Target Pressure Adjusting - LG MULTI V ARUN100LSH0 Installation Manual

Table of Contents

Advertisement

Target pressure adjusting

Mode setting method
Setting
low pressure
Mode
(kPa)
off
778
op1
699
op2
739
op3
843
op4
908
op5
961
op6
1 026
CAUTION
!
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• Change a power consumption or capacity.
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
Select the Function using '▶', '◀' Button :
"Fn8" Push the '●' button
"Fn8" Push the '●' button
Select the Option using '▶', '◀' Button :
"HEAT" , "COOL" Push the '●' button
Select the Option using '▶', '◀' Button :
"op1" ~ "op6" Push the '●' button
Target pressure is set
high pressure
(kPa)
2 990
3 121
2 827
2 696
2 565
2 435
2 304
ELECTRICAL WIRING
71