7) The rotary switch set value of above number of indoor units which is
connected with FF and prevents a malfunction.
(Example: The case where 3 indoor units is connected in piping 1,
sets from rotary switch 0,1,2 and 3,4,5,6,7 with FF set)
- Prerequisite for manual valve addressing: central control address of
each indoor unit must be preset differently at its wired remote con-
trol.
No.
Display and setup
- Operation: None
7-SEG
SW01E
1
- Display: None
0
SW02B
SW01B
SW01C
- Operation : Turn dip S/W No.1 on to ad-
dress valve #1
7-SEG
SW01E
2
- Display : Existing value saved in EEP-
0
ROM is displayed in 7-SEG.
SW02B
SW01B
SW01C
- Operation : Set the digit of 10(1) to the
number in Group High data of the wired
remote control connected to the corre-
7-SEG
SW01E
sponding indoor unit to the valve #1 by
3
0
pressing left tack S/W.
- Display : Digit increasing with the times
of pressing tack S/W is displayed in left
SW02B
SW01B
SW01C
7-SEG.
- Operation : SW01C : 1
7-SEG
SW01E
4
- Display : Display former value.
SW02B
SW01B
SW01C
- Operation : Setting No. using SW02B
7-SEG
SW01E
and SW01B, SW01C : 1
5
- Display : Display setting value.
SW02B
SW01B
SW01C
- Operation : Turn dip S/W No.1 off to save
the address of valve #1
7-SEG
SW01E
6
- Display : "11" displayed in 7-SEG disap-
pears.
SW02B
SW01B
SW01C
- Operation : Return valve of addressing
7-SEG
SW01E
HR unit.
7
0
- Display : None
SW02B
SW01B
SW01C
- Above setup must be done for all HR unit valves.
- The valve that is not connected with any indoor unit should be ad-
dressed with any other number than used address numbers of the
valves connected with indoor units.(The valves does not work if the
address numbers are same.)
Setup and Contents
Method of checking the pipe detection result
at HR unit
In case that an indoor unit of central control address "11" is connected to a
valve #1 of an HR unit
No.
Display and setup
1
7-SEG
SW01E
2
7-SEG
SW01E
Identification of Manual Valve ID (Address)
No.
Display and setup
1
7-SEG
SW01E
Setting the function
Select the mode/function/option/value using '▶', '◀' Button and con-
firm that using the '●' button after dip switch No.5 is turned on.
7-Segment
SW01C(●:confirm)
SW02C(◀:backward)
SW03C(▶:forward)
Setup and Contents
- Operation: Turn dip S/W No.1 on.
- Display: "11" is displayed in 7-SEG
- Operation: Turn dip S/W No.1 off.
- 7-SEG disappeared
Setup and Contents
- Operation: more than 2 dip switches
turned on.
- Display: "Er" is displayed in 7-SEG
SW01D(reset)
SW04C(x:cancel)
DIP-SWITCH
29