ELECTRICAL WIRING
68

Target pressure adjusting

Mode setting method
Setting
low pressure
Mode
off
op1
op2
op3
op4
op5
op6
CAUTION
!
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• Change a power consumption or capacity.
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
Select the Function using '▶', '◀' Button :
"Fn8" Push the '●' button
"Fn8" Push the '●' button
Select the Option using '▶', '◀' Button :
"HEAT" , "COOL" Push the '●' button
Select the Option using '▶', '◀' Button :
"op1" ~ "op6" Push the '●' button
Target pressure is set
high pressure
(kPa)
(kPa)
778
2,990
699
3,121
739
2,827
843
2,696
908
2,565
961
2,435
1,026
2,304