Table 1 MMX System Limits (Continued)
Device
14
Inputs correlated to
Remote Zones
15
Remote Output Zones
16
UDACTs
17
Custom Audio Clips
18
Entries in one audio
message (audio clips
and repeat loops
together)
19
Custom Digital
Messages
20
Custom Intervals
21
Custom Timers
22
Output Circuits
23
Input Zones
24
Proving Correlations
25
Manual Controls
26
Units in an Equation
27
Equations
28
Node groups
4.2

Frames

The frame is a measure of display capacity. The LCD annunciators and the main displays
provide frames, and the display boards (display adders) consume frames. The total number of
frames used by all the display boards connected to an annunciator must not exceed the
number of frames provided by that annunciator.
For example, the main display has 12 available frames, and the FDX-008 smoke control fan
damper module uses 1 frame. You can connect 12 FDX-008s to a main display if you connect
no other display boards. The RAX-1048 programmable zone/trouble LED uses 3 frames, so
you can connect 4 RAX-1048s to a main display. Or you can connect a combination of both,
for instance 2 RAX-1048s (6 frames) and 6 FDX-008s (6 frames).
Maximum number
1800 per CPU
1800 per CPU
1 per system
96 per system
32 per system
96 per system
60 per system
30 per system
318 per CPU
400 per CPU
100 per system
200 per system
999 per CPU
220 per system
127