CONFIGURING THE PANEL
When the system is installed and is ready to be commissioned, configuring the system consists of:
Use the CONFIG PANEL menu LEARN option - On initial commissioning; or following removal
or addition of external device(s) (sounder, call point, detector, etc.), set the system to
automatically learn what internal cards, external devices and RSUs are connected.
Set Common Output for HOLD and ABORT – On initial commissioning; or following removal
or addition of sounders, set any of the outputs for use as a common output indication, to show
activation of HOLD and ABORT functions.
Panel Setup (User menu) – Set Auto/Manual Modes, Display brightness, Internal Buzzer
volume, system Time and Date, etc.
Device Outputs (CONFIG Menu) – Set configuration options for the panel (sounder options,
reset password, set inhibit time, reset panel defaults, etc.), internal cards (timer options, etc.),
External Devices (device names, output options, etc.).
Extinguishant release (CONTROL Menu) – Set configurable options for extinguishant release,
including for FLOOD and EXTRACT.

Accessing the Menu Structure

Power-on the panel and wait for it to perform a routine status check. Any faults detected will be
displayed, accompanied by a warning tone. Press the Mute Buzzer button to silence the warning tone.
Resolve any faults before proceeding.
Next proceed by pressing the ✓ button, the LCD unit displays the following Access Level 2 Menu (see
picture below):
To access the menu structure:
Turn Activate Controls key switch clockwise to On
or
use the keypad to enter Authorised User (Access level 2) code 1111:
Press ✓ key to select Access level 2. The digital display will show the following message:
Enter Level 2 Access Code
o
Use Up/Down arrow keys to increase/decrease the number value
o
Use Left/Right arrow keys to move to the next digit in the 4-digit sequence
When all 4 digits have been set to the code 1111, press the ✓ key again
o
o
The LCD unit displays the Access Level 2 Main Menu (see picture below), which is
available for operation
Note: Access level 2 Menu will deactivate after 30 sec if not used.
CONFIGURING THE PANEL
Approved Document Ref: UI-ESG-01 Issue 2.0
41