Haes ESPRIT-G Installation, Commissioning & Operating Manual page 60

Fire control extinguishing panel
Table of Contents

Advertisement

ESPRIT Gas Extinguishing User Manual
CONFIG DEVICES Menu: RELAYS
To configure the Relay outputs:
On the CONFIG Menu, highlight Devices option and then press ✓ key to gain access to it.
On the CONFIG Devices sub-menu, highlight the Relay option and press the ✓ key again.
The information available under the CONFIG Relay sub-menu will be presented as follows:
CONFIG Relay
TWO / AREA ONE EXTRACT / AREA ONE LOCAL FIRE / AREA TWO Stage ONE
/ AREA TWO Stage TWO / AREA TWO EXTRACT / AREA TWO LOCAL FIRE>
1: GENERAL ALARM: CONTINUOUS / PULSING / OFF
2: PRE-ACTIVATED: CONTINUOUS / PULSING / OFF
3: ACTIVATED: CONTINUOUS / PULSING / OFF
4: RELEASED Stage: CONTINUOUS / PULSING / OFF
5: NON-CONTRIB ALARM: CONTINUOUS / PULSING / OFF
6: Relay ABORT OUTPUT: YES / NO
7: Relay HOLD OUTPUT: YES / NO
8: AREA 1 ALARM: YES / NO
9: AREA 2 ALARM: YES / NO
10: EVAC: CONTINUOUS / PULSING / OFF
11: FAULT: CONTINUOUS / PULSING / OFF
12: FAIL: YES / NO
13: EXTRACT AREA 1: YES / NO
14: EXTRACT AREA 2: YES / NO
Note: Single Flood Zone Panels will have 6 Relays (2 common Relays on the PSU Card –
FIRE and FAULT – and 4 Relays for the Gas Card). Dual Flood Zone Panels will have 10
Relays (2 common Relays on the PSU Card – FIRE and FAULT - and 4 Relays on each Gas
Card fitted).
Use Left/Right arrow keys to toggle between the various Relays (FIRE, FAULT, AREA ONE
Stage ONE, AREA ONE Stage TWO, etc.).
Use Up/Down arrow keys to select required Relay Output option.
Once selected, press the ✓ key to change indicated state.
Note: For options 1 to 5, 10 and 11, each press of ✓ key will toggle between the 3 available
states (CONTINUOUS, PULSING and OFF).
Note: For options 6 to 9, 12 to 14 pressing the ✓ key will toggle between YES and NO.
When finished, press the return
of buzzer beeps will indicate the changes have been stored in memory.
Further presses of return
<FIRE / FAULT / AREA ONE Stage ONE / AREA ONE Stage
key to return to CONFIG Devices Menu. A short sequence
key will exit back to Title screen.
Approved Document Ref: UI-ESG-01 Issue 2.0
CONFIGURING THE PANEL
60