Note: OFF will de-activate Test Mode function, so that any zones set for this mode will still activate
Fire Alarms in the standard way
When selection is made, press return
Test MODE Menu: SETTINGS
This menu is used to set which zone(s) are to be tested, along with Sounder option:
On the Main Menu, use Left/Right arrow keys to move cursor to ENG menu icon and press ✓
key to select.
From the ENG Menu, use Left/Right arrow keys to move curser to select Test sub-menu.
Press ✓ key to select.
On the Test MODE menu, use Left/Right arrow keys to select SETTINGS sub-menu. Press ✓
key to select.
The Test SETTINGS menu will display the following options:
-GENERAL-
1: SOUNDERS: EXCLUDED / TESTING
-GAS AREA ONE-
2: Zone ONE: EXCLUDED/TESTING
3: Zone TWO: EXCLUDED/TESTING
4: Zone THREE: EXCLUDED/TESTING
-GAS AREA TWO- (for twin Flood Zone panels)
5: Zone FOUR: EXCLUDED/TESTING
6: Zone FIVE: EXCLUDED/TESTING
7: Zone SIX: EXCLUDED/TESTING
Use the Up/Down arrow keys to select the required option.
Press ✓ key to toggle between Excluded and Testing.
Press return
key to accept and return to Test MODE sub-menu.
Press return
key to accept and return to ENG menu.
Note: The indicated states are either EXCLUDED (i.e. excluded from Test) or TESTING (i.e. included
in the Test). Any zones set to TESTING will create a non-latching fire alarm with unaffected Release
status when activated, without any sounder activation, unless sounders have been included in the test
in which case, they will all pulse twice then go silent. Sounders if set for testing will still operate normally
to fires detected on zones excluded from testing.
key to return to Test MODE sub-menu screen.
Approved Document Ref: UI-ESG-01 Issue 2.0