Haes ESPRIT-G Installation, Commissioning & Operating Manual page 55

Fire control extinguishing panel
Table of Contents

Advertisement

ESPRIT Gas Extinguishing User Manual
o
Press return
o
P-BUS: The LEARN PANEL sub-menu will display a list containing all 16 RSUs
and show if they are connected or not, using the P-BUS, indicated by the Gas
area the RSU is connected to, or NOT PRESENT:
-P-BUS-
1: FIRST RSU: GAS AREA ONE/GAS AREA TWO/NOT PRESENT
2: SECOND RSU: GAS AREA ONE/GAS AREA TWO/NOT PRESENT
3: THIRD RSU: GAS AREA ONE/GAS AREA TWO/NOT PRESENT
to
14: FOURTEENTH RSU: GAS AREA ONE/GAS AREA TWO/NOT PRESENT
15: FIFTEENTH RSU: GAS AREA ONE/GAS AREA TWO/NOT PRESENT
16: SIXTEENTH: GAS AREA ONE/GAS AREA TWO/NOT PRESENT
o
For each of the RSUs fitted, configure to show which Gas Area they are installed in:
Press the return
present.
Note: The status of the RSUs may be changed, using the Up/Down arrow keys and the ✓ key
to change between GAS AREA ONE, GAS AREA TWO or NOT PRESENT. However, any
differences between detected devices and changes made by user, will result in a System Fault
condition. The General Fault and System Fault status LEDs will be illuminated pulsing, with
an accompanying fault tone from the internal buzzer. Additionally, on return to the Title screen,
a FAULT display will list the applicable faults. This condition will require the panel to be re-
configured to clear.
CONFIG PANEL Menu: OPTIONS
To configure the panel sounder options, access the OPTIONS menu:
On the CONFIG Menu, highlight PANEL option and then press ✓ key to gain access to it.
Next highlight the OPTIONS icon, under the CONFIG PANEL menu and press ✓ key to select
it.
The information available under PANEL OPTIONS menu will be presented as follows (use the
up/down arrows key to navigate between following settings):
1: ZONES RESOUND 2ND ALARM: YES/NO
2: Sounder ONE FARE: YES/NO
3: Sounder TWO FFRE: YES/NO
4: RESET INHIBIT TIME (Min): nnnn
Use the Up/Down arrow keys to move between options 1 to 4
For options 1 to 3, press enter ✓ key to toggle between YES or NO, as required.
For option 4, press enter ✓ key to enable changes, then use Up/Down arrow keys to set
the time the sounders activation is to be inhibited by (up to a maximum of 30 minutes).
Press the ✓ key to exit RESET INHIBIT TIME adjustment function.
Note: If SOUNDER ONE FARE and/or SOUNDER TWO FFRE are set to YES, their status
(NORMAL/ACTIVE) will be displayed on the LCD screen title display, and in place of the event
counts (A nn F nn D nn O nn) on any of the EVENT reports (ALARM, FAULT, DISABLE and
OTHER).
key again
Use the Up/Down arrow keys to select each RSU to be configured
Press the enter ✓ key to toggle through the options, GAS AREA ONE/GAS
AREA TWO/NOT PRESENT,
key to finally accept. A short acknowledgement sound will be
CONFIGURING THE PANEL
Approved Document Ref: UI-ESG-01 Issue 2.0