gefran ADV200 WA Functions Description  And Parameters List

gefran ADV200 WA Functions Description And Parameters List

Field oriented vector ac drive
Table of Contents

Advertisement

Quick Links

Field oriented
vector AC Drive
ADV200 WA
....
Functions description
and parameters list

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ADV200 WA and is the answer not in the manual?

Questions and answers

Summary of Contents for gefran ADV200 WA

  • Page 1 Field oriented vector AC Drive ADV200 WA ..Functions description and parameters list...
  • Page 2: Information About This Manual

    Gefran S.p.A has the right to modify products, data and dimensions without notice. The data can only be used for the product description and they can not be understood as legally stated properti Thank you for choosing this Gefran product.
  • Page 3: Table Of Contents

    27.4 I/O FOLLOWER ....................................184 27.5 TIMER ........................................186 27 – MACRO ..............................187 27.1 – MACRO Selection....................................187 27.2 – HVAC Standard ....................................188 27.3 – Supply FAN ......................................191 27.4 – Return FAN ......................................194 ADV200 WA • Functions description and parameters list...
  • Page 4 Multireference ..............................276 Motorpotentiometer.............................277 Jog function ................................277 Monitor function ..............................278 Commands .................................280 Digital inputs ...............................282 Digital outputs ..............................283 Analog inputs ..............................284 Analog outputs ..............................286 Speed reg gains..............................287 VF parameters ..............................288 Functions ................................289 Process ................................293 ADV200 WA • Functions description and parameters list...
  • Page 5: A - Programming

    The analog and digital signals come from the terminal strip of the regulation card and/or from those of the expansion cards. 2 – Drive internal variables Internal drive control system variables, from “function block” calculations, sent via keypad, PC configurator or fieldbus. ADV200 WA • Functions description and parameters list...
  • Page 6 The Ramp ref invert src parameter (PAR: 616) can be used to select the source for the command to reverse the “Ramp setpoint” function block output. The output signal from the “Ramp setpoint” block is displayed in the Ramp ref 1 mon parameter (PAR: 620). ADV200 WA • Functions description and parameters list...
  • Page 7: B - Parameters And Functions Description (Expert List)

    The source of the signal that will control the parameter can be selected from the list indicated.  The lists are indicated in paragraph C of this manual. Format of data exchanged on Fieldbus (16BIT, 32BIT) ADV200 WA • Functions description and parameters list...
  • Page 8: Monitor

    The actual output speed of the motor is displayed (in Flux vector OL/V/f control = speed estimated by the drive). Menu Description Type FB BIT DC link voltage FLOAT 16/32 The direct voltage of the intermediate circuit capacitors is displayed (DC-Bus). ADV200 WA • Functions description and parameters list...
  • Page 9 0 Disabled drive disabled 1 Enabled drive enabled Menu Description Type FB BIT 1.19 1068 Start state mon The drive Start command status is displayed. ADV200 WA • Functions description and parameters list...
  • Page 10 The data are contained in a word, where each bit is 1 if voltage is supplied to the corresponding input terminal. 1 Output enabled. 0 Output disabled. 000000000011 I.e. : Attiva DO 2 Attiva DO 1 ADV200 WA • Functions description and parameters list...
  • Page 11: Drive Info

    355.0 kW 690V 400.0 kW 690V 500.0 kW 690V 630.0 kW 690V 710.0 kW 690V 800.0 kW 690V 1000.0 kW 690V 1200.0 kW 690V 160.0/200.0 kW 690V 200.0/250.0 kW 690V 250.0/315.0 kW 690V ADV200 WA • Functions description and parameters list...
  • Page 12 When the parameter is read via serial line or fieldbus the version is returned in the high byte and the release in the low byte. Menu Description Type FB BIT Application type UINT16 The type of application currently used by the drive is displayed. ADV200 WA • Functions description and parameters list...
  • Page 13 None 769 I/O 1 1793 I/O 2 2305 I/O 3 3329 I/O 4 7681 I/O 8 (EXP-IO-SENS-1000-ADV) 5633 I/O 6 (EXP-IO-SENS-100-ADV) 6401 I/O 7 (EXP-IO-D5R8-ADV) Can/Dnet 260 Profibus 516 RTE 255 Unknown ADV200 WA • Functions description and parameters list...
  • Page 14: Startup Wizard

    The startup wizard menu suggests a procedure for commissioning the drive quickly with a reduced number of settings. Advanced customization requires the use of the single parameters relating to the specific performance levels. See the procedure described in the Startup wizard chapter in Quick Start ADV200-WA -QS manual. ADV200 WA • Functions description and parameters list...
  • Page 15: Drive Config

    Setting the parameter to Expert gives access to all the parameters in the firmware. This mode allows an ex- tremely high level of customization to be achieved in order to exploit the potential of the ADV200 to the full. ADV200 WA • Functions description and parameters list...
  • Page 16 560 Mains voltage are calculated on the basis of the voltage shown in the table below, while the value of parameter 560 Tensione di rete is set automatically. If “None” is selected, these parameters are calculated according to the value of parameter 560 Mains voltage. ADV200 WA • Functions description and parameters list...
  • Page 17 1 50 degC The inverter is capable of delivering direct current continuously with ambient temperatures of up to 50°C. If the value is set to 1 the drive output current will be 10% less than the rated current at 40°C. ADV200 WA • Functions description and parameters list...
  • Page 18 This parameter can be used to enter the key for enabling the PLC application. You may need to enter a key to definitively enable some PLC applications. Please contact Gefran for details ADV200 WA • Functions description and parameters list...
  • Page 19 In this phase a message is displayed informing you that the period of forced enabling time is about to expire. At the first power-on after the 200 hours an alarm is generated and the application does not start. Please contact Gefran for the numerical value of the key. Menu...
  • Page 20: References

    “Multispeed” functions are selected the relative references are used. In Remote mode the overall ramp reference is the result of the sum of the values with the Ramp ref 1 and Ramp ref 2 sign. ADV200 WA • Functions description and parameters list...
  • Page 21 INT16 The value of the relative ramp reference on the output of the relative function block is displayed. Menu Description Type FB BIT 5.11 Ramp ref top lim INT32 CALCI ERWZ VS ADV200 WA • Functions description and parameters list...
  • Page 22 ERW VS 5.16 Reference skip band1 INT16 CALCI 5.18 Reference skip band2 INT16 CALCI Setting of the prohibited bandwidth. Reference out Par. 632 Par. 632 Par. 630 Par. 630 Reference in Example: ADV200 WA • Functions description and parameters list...
  • Page 23 The overall speed reference is the result of the sum of the values, with sign, of Speed ref 1 and Speed ref 2. Example 1: Speed ref 1 = + 500 rpm Speed ref 2 = + 300 rpm Speed ref = 500 rpm + 300 rpm = 800 rpm ADV200 WA • Functions description and parameters list...
  • Page 24 Full scale speed does not define the maximum possible speed. In any case, the maximum speed percentage value is ± 200 % of the Full scale speed value. ADV200 WA • Functions description and parameters list...
  • Page 25: Ramps

    (6.2, 6.4, 6.6, 6.8 ) are expressed as the time necessary to bring the frequency from the maximum value set in the Full scale speed (5.22) parameter to zero. Each of the 4 available ramp selections can be selected us- ing one or two digital inputs programmed as Multi ramp sel. ADV200 WA • Functions description and parameters list...
  • Page 26 Deceleration time 2 Acceleration time 3 Deceleration time 3 Menu Description Type FB BIT 6.12 Multi ramp sel mon UINT16 The set of acceleration/deceleration ramps selected using the digital inputs is displayed. ADV200 WA • Functions description and parameters list...
  • Page 27 Selection of the origin (source) of the signal that temporarily freezes the ramp output value, regardless of any changes in the input reference. The terminal to be associated with this function can be selected from the “L_DIGSEL2” selection list. Ramp freeze Ramp Output (Motor speed) ADV200 WA • Functions description and parameters list...
  • Page 28: Multi Reference

    CALCI Multi reference 1 INT16 16/32 CALCI CALCI Multi reference 2 INT16 CALCI CALCI Multi reference 3 INT16 CALCI CALCI Multi reference 4 INT16 CALCI CALCI Multi reference 5 INT16 CALCI CALCI ADV200 WA • Functions description and parameters list...
  • Page 29 Multi reference 3 Multi reference 4 Multi reference 5 Multi reference 6 Multi reference 7 Multi reference 8 Multi reference 9 Multi reference 10 Multi reference 11 Multi reference 12 Multi reference 13 ADV200 WA • Functions description and parameters list...
  • Page 30 The multispeed that has been selected using the digital commands or by the digital inputs selected in the terminal strip. Menu Description Type FB BIT 7.24 Multi ref out mon INT16 16/32 The selected speed reference on the Multispeed block output is displayed. ADV200 WA • Functions description and parameters list...
  • Page 31: Motorpotentiometer

    FB BIT Mpot setpoint INT16 16/32 CALCI CALCI The speed reference value of the Motor potentiometer function is displayed. Enter this parameter to send the UP and DOWN commands from the keypad. ADV200 WA • Functions description and parameters list...
  • Page 32 5 Output = 0 6 Output = low lim 7 Output & ref = 0 8 Output & ref = low lim 9 Input = upp lim Input & ref = upp lim Freeze input ADV200 WA • Functions description and parameters list...
  • Page 33 ERW VS Selection of the origin (source) of the signal to preset the motor potentiometer function. The signal to be as- sociated with this function can be selected from the “L_DIGSEL2” selection list. ADV200 WA • Functions description and parameters list...
  • Page 34 In Ramp mode, each time the Up or Down commands are enabled, the output of the Motor potentiometer function increases or decreases with the set ramp. When the Up or Down command is removed, the last value that was reached is maintained. ADV200 WA • Functions description and parameters list...
  • Page 35 FB BIT 8.13 Mpot output mon INT16 16/32 The value of the output of the motor potentiometer function is displayed. Two examples of application of the motor potentiometer function are shown below. ADV200 WA • Functions description and parameters list...
  • Page 36 Fine&Last Val. Each time they are pressed for 1 second, the speed increases by 1 rpm. For an immediate effect on motor speed, the Acceleration time and Deceleration time parameters should be set to short times. ADV200 WA • Functions description and parameters list...
  • Page 37: Jog Function

    Note ! The Run command has priority over the Jog - command. Menu Description Type FB BIT Jog output mon INT16 16/32 The speed reference used by the Jog command is displayed. ADV200 WA • Functions description and parameters list...
  • Page 38: Monitor Function

    Setting of the delay in milliseconds after which the speed = 0 reached signal is enabled. n = 0 When the motor reaches a speed that is below the zero speed threshold, it stops and the LED lights up. ADV200 WA • Functions description and parameters list...
  • Page 39 Set speed error parameter, after which the transition from 0 c1 is enabled. The transition of the Set Speed signal from 0 c1 is always immediate. Menu Description Type FB BIT 10.11 Dig set speed ref UINT16 16/32BIT CALCI CALCI ADV200 WA • Functions description and parameters list...
  • Page 40 If the threshold value is lower than the value set in 982 Current thr hyster, the result produced is always 0. The value set in this parameter is active in both directions of rotation. ADV200 WA • Functions description and parameters list...
  • Page 41 If the threshold value is lower than the value set in 982 Current thr hyster, the result produced is always 0. The value set in this parameter is active in both directions of rotation. ADV200 WA • Functions description and parameters list...
  • Page 42: Commands

    Alternatively, the value of 6000 can be written directly on the Digital Enable src and Digital Start src parameters for a source of Null (0) or the value of 6002 for a source of One (1). ADV200 WA • Functions description and parameters list...
  • Page 43 Start key. When Keypad is set to generate the Enable cmd mon command, as well as the Start key the enable hardware command must also be sent to the Enable terminal (7). ADV200 WA • Functions description and parameters list...
  • Page 44 Stop terminal is not enabled. In Terminal mode the drive is instantly disabled if there is no signal on the Enable terminal, or when the speed=0 is reached if the terminal programmed as FastStop is enabled. ADV200 WA • Functions description and parameters list...
  • Page 45 Menu Description Type FB BIT 11.8 1014 Local/remote src LINK 1012 16384 ERW VS Selection of the origin (source) of the signal that switches between Remote and Local. Switching can only be ADV200 WA • Functions description and parameters list...
  • Page 46 1026 Start cmd mon The status of the Start command is displayed. Menu Description Type FB BIT 11.15 1028 FastStop cmd mon This parameter is used to display the value of the FastStop command state. ADV200 WA • Functions description and parameters list...
  • Page 47 FR Reverse command is present the motor rotates in the reverse direction, The FR start mon output repeats the status of the FR Forward command, while the FR reverse mon output repeats the status of the FR Reverse command. ADV200 WA • Functions description and parameters list...
  • Page 48 The motor rotates in the Reverse direction for as long as the FR Reverse signal is enabled. If the FR Reverse signal is disabled the motor rotates in the Forward direction. To stop the motor open the FR *stop contact. ADV200 WA • Functions description and parameters list...
  • Page 49 11.22 1052 FR cdm mon UINT16 The status of the commands of the Forward Reverse Control (FRC) block are displayed. FR *stop src FR reverse src FR forward src FR cdm mon ADV200 WA • Functions description and parameters list...
  • Page 50: Digital Inputs

    12 – DIGITAL INPUTS Note: The numbering and description of the following parameters may change if an MDPLc application is active. ADV200 WA • Functions description and parameters list...
  • Page 51 1280 Dig input 6X dest ILINK 12.26 1282 Dig input 7X dest ILINK 12.27 1284 Dig input 8X dest ILINK Selection of the destination of the associated digital input of the expansion card. ADV200 WA • Functions description and parameters list...
  • Page 52: Digital Outputs

    13 – DIGITAL OUTPUTS Note: The numbering and description of the following parameters may change if an MDPLc application is active. ADV200 WA • Functions description and parameters list...
  • Page 53 1442 Dig out 7X inversion 13.25 1444 Dig out 8X inversion 13.26 1446 Dig out 9X inversion Reversal of the logic status of the function associated with the digital output of the expansion card. ADV200 WA • Functions description and parameters list...
  • Page 54: Analog Inputs

    FB BIT 14.3 1504 Analog inp 1 scale FLOAT -10.0 10.0 14.19 1554 Analog inp 2 scale FLOAT -10.0 10.0 Setting of a multiplier factor to apply to the relative analog input. ADV200 WA • Functions description and parameters list...
  • Page 55 (not considering the Analog inp scale parameter) to reach the full scale value. If the voltage setting on the analog input is less than 1V, the Value too low alarm is generated. ADV200 WA • Functions description and parameters list...
  • Page 56 The maximum analog value available (in this case 9.8V) must be present on the terminal, with positive polarity. Press the Enter key on the keypad to start analog reference self-tuning. ADV200 WA • Functions description and parameters list...
  • Page 57 Setting of a fixed alternative value for the relative analog input, which can be selected via a command enabled by a digital input programmed with the An inp alt sel src parameter. ADV200 WA • Functions description and parameters list...
  • Page 58 -10V..+10V 14.45 1652 Analog inp 2X type ENUM -10V..+10V Selection of the type of expansion card input (voltage or current input). In the default configuration the inputs are coded for voltage signals. ADV200 WA • Functions description and parameters list...
  • Page 59 When this command is sent, An inp xX offset tune is automatically selected so that the available input signal corresponds to the zero value of the variable. Automatic tuning can only be performed if the following condition is present: ADV200 WA • Functions description and parameters list...
  • Page 60 1666 Analog inp 2X offset INT16 -32768 + 32767 ERW VS Setting of an offset value to algebrically add to the relative analog input of the expansion card. 100% Analog inp xX offset ADV200 WA • Functions description and parameters list...
  • Page 61 1632 Analog inp 1X dest ILINK 14.54 1682 Analog inp 2X dest ILINK The function for which the relative analog input of the expansion card has been programmed and on which it acts is displayed. ADV200 WA • Functions description and parameters list...
  • Page 62: Analog Outputs

    Selection of the origin (source) of the signals that can be placed as variables on the analog outputs. The func- tions that can be assigned to the analog outputs are listed in the “L_ANOUT” selection list. ADV200 WA • Functions description and parameters list...
  • Page 63 Enables the relative analog output as an absolute value. If this parameter is set to 1 the voltage on the analog output assumes the value of 0 - 10V regardless of the sign of the command signal. 0 Disable 1 Enable ADV200 WA • Functions description and parameters list...
  • Page 64 Parameter for setting a multiplier factor of the signal of the relative analog output of the expansion card. It can be used to amplify or reduce the input value of the relative analog output block. ADV200 WA • Functions description and parameters list...
  • Page 65 1884 Analog out 1X max INT16 16384 -32768 +32767 ERW VS Setting of the minimum and maximum values for the analog output for the voltage present on analog output 1 of the expansion card. ADV200 WA • Functions description and parameters list...
  • Page 66 1892 Analog out 2X max INT16 16384 -32768 +32767 ERW VS Setting of the minimum and maximum values for the analog output in current or voltage present on analog output 2 of the expansion card. ADV200 WA • Functions description and parameters list...
  • Page 67: Motor Data

    Rated speed of the motor with full load in rpm. In some motors the synchronous speed (e.g. 1500 rpm for a 4-pole motor) and slippage, i.e. the loss of revolutions between the motor idling condition and the rated load condition (e.g. 80 rpm), is indicated. Enter the following: synchronous speed - slippage. ADV200 WA • Functions description and parameters list...
  • Page 68 RWZ VS Performs self-tuning with the motor coupled to the transmission. The self-tuning procedure may cause limited rotation of the motor shaft. To perform self-tuning, follow the procedure described for the previous parameter. ADV200 WA • Functions description and parameters list...
  • Page 69 16.18 2058 Measured ImN FLOAT CALCF 1500.0 ERWS VS Measured rated magnetizing current value. Menu Description Type FB BIT 16.19 2060 Measured ImX FLOAT CALCF ERWS VS Measured magnetizing current saturation value. ADV200 WA • Functions description and parameters list...
  • Page 70 Saves the motor data calculated by the self-tuning procedure in the drive. Note ! Data are not saved permanently. Use the “Save Parameters” command in the DRIVE CONFIG menu to save in the permanent memory. ADV200 WA • Functions description and parameters list...
  • Page 71: Speed Reg Gains

    “L_REF” selection list. Menu Description Type FB BIT 18.6 2218 Gain adapt spd thr 1_2 perc FLOAT 100.0 ERW _S Setting of the speed threshold for changing gains from set 1 to set 2. ADV200 WA • Functions description and parameters list...
  • Page 72 Setting of the proportional coefficient of the speed regulator. Menu Description Type FB BIT 18.14 2238 Speed reg I time FLOAT CALCF 5000.0 ERWS _S Setting of the integral coefficient of the speed regulator. ADV200 WA • Functions description and parameters list...
  • Page 73 Type FB BIT 18.16 2242 Bandwidth rad/s FLOAT SIZE 500.0 RWZS _S Setting of the bandwidth. Increasing the setting of this parameter increases the dynamic response and makes the system more rigid. ADV200 WA • Functions description and parameters list...
  • Page 74: Regulator Param

    The dead time compensation function (Dead time compensation), compensates the distortion of output volt- age caused by the voltage drop on the IGBT devices and their switching characteristics. Distortion of output voltage could cause irregular motor rotation. ADV200 WA • Functions description and parameters list...
  • Page 75 In case of instability, try changing the value and setting half or twice the default value. Menu Description Type FB BIT 19.17 2308 OverFlux perc perc FLOAT 100.0 100.0 140.0 ERW __S The value is expressed as the percentage in excess of the rated flux. ADV200 WA • Functions description and parameters list...
  • Page 76 2320 Magnetization time UINT16 4096 ERWZ __S This parameter is used to slow down the magnetisation transient and prevent the motor shaft from rotating due to the alignment of the stator and rotor. ADV200 WA • Functions description and parameters list...
  • Page 77: Fv Parameters

    This is the frequency at which the drive output voltage reaches the maximum output voltage (Vf voltage) on the motor. Menu Description Type FB BIT 21.6 2410 Vf voltage 1 FLOAT CALCF CALCF CALCF ERWZS V Setting of an intermediate voltage value for the custom V/f characteristic curve. ADV200 WA • Functions description and parameters list...
  • Page 78 When this type of curve is selected, the median voltage point is fixed at 0.25% of the maximum output voltage (par.2406), and the median frequency point at 50% of the basic frequency (par.2408). ADV200 WA • Functions description and parameters list...
  • Page 79 When set to 0 (Open loop) the slip compensation value is that set manually in parameter 5210 or calculated by the self-tuning procedure. Menu Description Type FB BIT 21.13 2446 Slip P gain perc FLOAT 100.0 ERWS V Setting of the slip compensation proportional gain. ADV200 WA • Functions description and parameters list...
  • Page 80 It is not possible to go below this value, regardless of the reference that has been set. Menu Description Type FB BIT 21.21 2482 Vf min freq delay UINT16 5000 ERW V ADV200 WA • Functions description and parameters list...
  • Page 81 ERW V Selection of the origin (source) of the signal to be used to set a multiplier factor for the drive output voltage. The associable functions are listed in the “L_REF” selection list. ADV200 WA • Functions description and parameters list...
  • Page 82: Functions

    0-32.000 100 100 1000 1000 Menu Description Type FB BIT 22.1.4 3010 Speed ratio mon FLOAT INT16 The speed ratio value to apply to the selected speed reference signal value is displayed. ADV200 WA • Functions description and parameters list...
  • Page 83: Functions/Inertia Comp

    Setting of a filter on the torque compensation. The filter reduces noise due to speed differentiation in the inertia block. Menu Description Type FB BIT 22.2.3 3104 Inertia comp mon perc FLOAT 16/32 The value of inertia compensation on the function block output is displayed. ADV200 WA • Functions description and parameters list...
  • Page 84: Functions/Dc Braking

    22.3 – FUNCTIONS/DC BRAKING ADV200 WA • Functions description and parameters list...
  • Page 85 PAR 3158 DC brake current is used to configure the intensity of the injection phase current. If the command is an impulse shorter than the time set with PAR 3156 Durata frenatura DC, the direct cur- ADV200 WA • Functions description and parameters list...
  • Page 86 During the direct current injection phase, for the Jog command follow the instructions provided for the Enable command. ADV200 WA • Functions description and parameters list...
  • Page 87: Functions/Motor Overload

    ERW VS Enabling of the motor overload control. 0 Disable 1 Enable If set to 0 the MOTOR OVERLOAD function is disabled. If set to 1 the MOTOR OVERLOAD function is enabled. ADV200 WA • Functions description and parameters list...
  • Page 88 MOTOR OVERLOAD protection intervention time must be reduced as cooling is insufficient. At below (PAR 2004 Rated speed / 2) the protection intervention time is reduced by reducing the direct current of the MOTOR OVERLOAD function. ADV200 WA • Functions description and parameters list...
  • Page 89 We recommend setting parameter 3218 Motor derat factor to a value so that Rated current (PAR 2002) * Motor service factor (PAR 3206) * Motor derat factor (PAR 3218) produces a result that is more than the motor magnetisation current. ADV200 WA • Functions description and parameters list...
  • Page 90: Functions/Bres Overload

    Setting of the external resistor overload factor. Menu Description Type FB BIT 22.5.5 3258 Bres overload time FLOAT SIZE 50.0 ERWS VS Setting of the intervention time of the external braking resistor overload. ADV200 WA • Functions description and parameters list...
  • Page 91: Functions/Speed Capture

    Drive enabled and demagnetising for a time < Par 3376 Vf catch Last frequency before disabling the drive lastref dly Automatic restart after an alarm Last frequency before the alarm occurred ADV200 WA • Functions description and parameters list...
  • Page 92 Menu Description Type FB BIT 22.6.4 3368 Vf catch search time FLOAT 30.0 ERW V This parameter is used to configure the speed at which the output frequency changes for synchronisation with ADV200 WA • Functions description and parameters list...
  • Page 93 If the time that elapses from the moment the drive is disabled exceeds the time set in this parameter, the capture procedure starts from the frequency set in parameter 3364 Vf catch start freq. ADV200 WA • Functions description and parameters list...
  • Page 94: Functions/Power Loss

    The master drive is normally the one that controls the load with the highest inertia. The master drive sends the Powerloss nextratio signal with the ADV200 WA • Functions description and parameters list...
  • Page 95 Ramp down Powerloss Next ratio PowerLoss_01.vsd Menu Description Type FB BIT 22.7.1 3400 Powerloss function ENUM Disable ERWZ F__ This parameter is used to enable the Powerloss function. 0 Disable 1 Enable ADV200 WA • Functions description and parameters list...
  • Page 96 The drive does not automatically recognise the fact that the mains supply has been re- stored. This information must be supplied from the outside via the Powerloss mains src digital input. 0 Ramp down 1 Restart ADV200 WA • Functions description and parameters list...
  • Page 97 The mains supply is not restored while the function is enabled Power supply The drive switches itself off if the power supply is not restored Speed ref Speed Speed ref Speed Powerloss Next active Powerloss Ramp down Powerloss Next ratio PowerLoss_02.vsd ADV200 WA • Functions description and parameters list...
  • Page 98 Ramp down and mains supply restored Drv enable The mains supply is restored while the function is enabled Power supply Speed ref Speed Speed ref Speed Powerloss Next active Powerloss Ramp down Powerloss Next ratio PowerLoss_03.vsd ADV200 WA • Functions description and parameters list...
  • Page 99 The mains supply is not restored while the function is enabled Power supply The drive switches itself off if the power supply is not restored Speed ref Speed Speed ref Speed Powerloss Next active Powerloss Ramp down Powerloss Next ratio PowerLoss_04.vsd ADV200 WA • Functions description and parameters list...
  • Page 100 This parameter is used to select the origin (source) of the Mains voltage OK signal. The signal to be associ- ated with this function can be selected from the “L_DIGSEL2” selection list. ADV200 WA • Functions description and parameters list...
  • Page 101: Functions/Compare

    Menu Description Type FB BIT 22.8.5 3670 Compare function ENUM None ERW VS Setting of the compare function between Compare input 2 and Compare input 1 to enable Cmp output. 0 None ADV200 WA • Functions description and parameters list...
  • Page 102 FB BIT 22.8.8 3676 Compare output The status of the comparator output is displayed: 0 The result of the set comparison is negative 1 The result of the set comparison is positive ADV200 WA • Functions description and parameters list...
  • Page 103: Functions/Pads

    INT32 32 ERW VS Setting of general, 32 Bit variables. PAD parameters can be used as supporting parameters to send values written by the fieldbus, serial line, etc. to analog or digital outputs. ADV200 WA • Functions description and parameters list...
  • Page 104: Functions/Vdc Control

    Vdc control function Setting of the integral time used during the . The set value must be reduced if the DC link voltage is set to a value other than the setpoint. ADV200 WA • Functions description and parameters list...
  • Page 105: Functions/Brake Control

    Setting of the delay for mechanical opening of the brake Menu Description Type FB BIT 22.11.3 3174 Brake close delay FLOAT 0.20 60.0 ERW VS Setting of the delay to reach the motor zero speed before closing the brake. ADV200 WA • Functions description and parameters list...
  • Page 106: Functions/Vf Energy Save

    This parameter can be changed if there are small, continuous changes in the speed of the speed reference to avoid continuously entering/leaving the output voltage reduction condition. ADV200 WA • Functions description and parameters list...
  • Page 107 V/f curve must be restored. Menu Description Type FB BIT 22.12.2 3340 Energysave out FLOAT 16/32BIT This parameter is used to read the request to reduce the output voltage. ADV200 WA • Functions description and parameters list...
  • Page 108: Functions/Rtc_Set

    Setting/modification of the current second Menu Description Type FB BIT 22.13.8 3992 Rtc calibration INT16 ERW VS This parameter is used to gauge the real-time clock counting speed, if the clock is not accurate enough. ADV200 WA • Functions description and parameters list...
  • Page 109: Communication

    3808 Serial swap data ERW VS This parameter enables the exchange of the reading of the High and Low parts of the words for FLOAT, UINT32, INT32 type parameters when using the Modbus protocol. ADV200 WA • Functions description and parameters list...
  • Page 110: Communication/Fieldbus Config

    If set to 0, the possibility of sending commands and references from the drive PLC via the fieldbus is disabled. If set to 1 the possibility of sending commands and references from the drive PLC via the fieldbus is enabled. ADV200 WA • Functions description and parameters list...
  • Page 111: Communication/Fieldbus M->S

    NICATION/FIELDBUS M2S menu, hence the name of the M->S menu: Parameter for setting input data: It must contain a valid IPA corresponding to the parameter to be written, or 0 if sys (PAR 4022...4172 Fieldbus M->Sn ADV200 WA • Functions description and parameters list...
  • Page 112 Fieldbus = 0, PAR 4042 Fieldbus M->S3 sys = Count16, PAR 4050 Fieldbus M->S4 ipa = IPA of the parameter that was previously in 3 and PAR 4052 Fieldbus M->S4 sys = Count32, thus using a first PDO with 6 bytes), or by creating ADV200 WA • Functions description and parameters list...
  • Page 113 23.3.57 4160 Fieldbus M->S15 ipa FBM2SIPA 20000 23.3.61 4170 Fieldbus M->S16 ipa FBM2SIPA 20000 Setting of the parameter to associate with the bus channel. The default setting is 0, which means channel not active. ADV200 WA • Functions description and parameters list...
  • Page 114 If set to 9, the datum is assigned a 16-bit integer engineering unit format not in real time (5-10ms) If set to 10 the datum is assigned a 32-bit integer engineering unit format or float format if the associated parameter is a float-type parameter not in real time (5-10ms) ADV200 WA • Functions description and parameters list...
  • Page 115 EU and EU_float exchange mode. The parameter value is used by the drive as the divider of the incoming datum, so that a number with decimal digits can be transferred. ADV200 WA • Functions description and parameters list...
  • Page 116: Communication/Fieldbus S->M

    23.4.25 4240 Fieldbus S->M7 ipa FBM2SIPA 20000 23.4.29 4250 Fieldbus S->M8 ipa FBM2SIPA 20000 23.4.33 4260 Fieldbus S->M9 ipa FBM2SIPA 20000 23.4.37 4270 Fieldbus S->M10 ipa FBM2SIPA 20000 23.4.41 4280 Fieldbus S->M11 ipa FBM2SIPA 20000 ADV200 WA • Functions description and parameters list...
  • Page 117 If set to 6 the datum is assigned a 32-bit count used by MDPLC. If set to 7 the datum is assigned engineering units on a 16-bit integer. If set to 8 the datum is assigned engineering units on a 32-bit integer. ADV200 WA • Functions description and parameters list...
  • Page 118 The “Fieldbus S->Mx mul” parameters are multipliers that the drive applies to the datum before sending it to the bus. It is therefore possible to increase the resolution of some values read in EU and EU_float mode, also using decimal digits. ADV200 WA • Functions description and parameters list...
  • Page 119: Communication/Word Comp

    ......Word bit14 src BIT_14 BIT_15 Word bit15 src Menu Description Type FB BIT 23.5.17 4432 Word comp mon UINT32 16 The hexadecimal value of the Word comp output is displayed. ADV200 WA • Functions description and parameters list...
  • Page 120: Communication/Word Decomp

    23.6.14 4476 Bit11 decomp mon 23.6.15 4478 Bit12 decomp mon 23.6.16 4480 Bit13 decomp mon 23.6.17 4482 Bit14 decomp mon 23.6.18 4484 Bit15 decomp mon The single bits that make up the selected word are displayed. ADV200 WA • Functions description and parameters list...
  • Page 121: Alarm Config

    Activity = Ignore or Warning can be enabled at the same time. If an alarm with Activity = Stop or Fast Stop is enabled and another alarm with an Activity other than Ignore or Warning is enabled, the drive stops and is disabled. ADV200 WA • Functions description and parameters list...
  • Page 122 Setting of the behaviour of the drive in the event of an external fault alarm ExtFlt. This alarm indicates the intervention of a drive external protection. 0 Ignore 1 Warning 2 Disable 3 Stop 4 Fast stop ADV200 WA • Functions description and parameters list...
  • Page 123 Menu Description Type FB BIT 24.12 4530 Motor OT probe ENUM Selection of the motor temperature sensor. Motor overtemperature can be controlled by the PT100, KTY and ADV200 WA • Functions description and parameters list...
  • Page 124 Speed ref top lim and Speed ref bottom lim param- eters in the COMMANDS menu. 0 Ignore 1 Warning 2 Disable 3 Stop 4 Fast stop ADV200 WA • Functions description and parameters list...
  • Page 125 ERW VS Setting of the behaviour of the drive in case of a braking resistor overload alarm Bres ovld. This alarm indi- cates that the braking resistor overload threshold has been reached. ADV200 WA • Functions description and parameters list...
  • Page 126 ENUM Disable ERW VS Enabling of automatic restart after the desaturation alarm Desat. This alarm indicates a short circuit between the motor phases or on the power bridge. 0 Disable 1 Enable ADV200 WA • Functions description and parameters list...
  • Page 127 Setting of the time within which, if no automatic restarts are executed after the Undervoltage alarm, the at- tempts counter is reset. In this way the number of attempts set in UVRep attempt are still available. ADV200 WA • Functions description and parameters list...
  • Page 128 Setting of the alarm signal to enable on a digital output. The digital output is selected using parameters Alm dig out mon 1÷4, which can be enabled in the L_DIGSEL1 selection list. 0 No alarm 1 Overvoltage ADV200 WA • Functions description and parameters list...
  • Page 129 Setting of the behaviour of the drive if the Broken belt alarm is present. The belt broken condition occurs if the torque required of the motor falls below a set threshold value. ADV200 WA • Functions description and parameters list...
  • Page 130 This is because if the pump is dry, there is no pressure in the system and the PID will increase to maximum speed. 0 Ignore 1 Warning 2 Disable 3 Stop 4 Fast stop ADV200 WA • Functions description and parameters list...
  • Page 131 0 Ignore 1 Warning 2 Disable 3 Stop 4 Fast stop Menu Description Type FB BIT 24.67 7818 Analog 1 err delay FLOAT Setting of the delay after which the alarm is activated. ADV200 WA • Functions description and parameters list...
  • Page 132 0 Ignore 1 Warning 2 Disable 3 Stop 4 Fast stop Menu Description Type FB BIT 24.73 7830 Analog 2x err delay UINT16 Setting of the delay after which the alarm is activated. ADV200 WA • Functions description and parameters list...
  • Page 133: Alarm Log

    Alarm number 1 PhaseLoss Alarm description 16/12/11 09:51 0000H 2 Undervoltage 16/12/11 09:50 0000H code Time and Hour alarm occurred Ilim n=0 3 SpdFbkLoss 15/12/11 16:27 0000H 4 Overspeed 15/12/11 11:02 0000H ADV200 WA • Functions description and parameters list...
  • Page 134: Process

    This parameter is used to adjust reference 1 and 2 analog input signals for the PID1 controller: 0 Ref1 1 Ref2 2 Src selection 3 Ref1+Ref2 4 Ref1-Ref2 5 Aver ref1 ref2 ADV200 WA • Functions description and parameters list...
  • Page 135 26.1.12 7324 PID 1 fbk function ENUM Fbk1 Selection of the operation to be executed on feedback signals 1 and 2 for the PID 1 controller: 0 Fbk1 1 Fbk2 2 Fbk1+Fbk2 ADV200 WA • Functions description and parameters list...
  • Page 136 The current value of the selected feedback is displayed. Menu Description Typo FB BIT 26.1.15 7330 PID 1 process unit ENUM Use this parameter to select the unit of measure used in the process. 2 rpm 3 ppm ADV200 WA • Functions description and parameters list...
  • Page 137 6 l/m 7 l/h 8 kg/s 9 kg/m kg/h m3/s m3/m m3/h mbar m ca °C °F gal/s gal/m gal/h lb/s lb/m lb/h ft3/s ft3/m ft3/h ft/s in wg ft wg Lb/i2 ADV200 WA • Functions description and parameters list...
  • Page 138: Process/ Pid 1

    In this condition the drive reacts more quickly once the PID 1 controller output returns to within the limits. Menu Description Typo FB BIT 26.2.4 7606 PID 1 P gain FLOAT 16/32BIT 10.0 100.0 Setting of the integral gain of the PID 1 controller. ADV200 WA • Functions description and parameters list...
  • Page 139 6) Set the range of values allowed for the feedback acquired by the transducer, by setting the values in parameters 7628 PID 1 fbk tune min and 7630 PID 1 fbk tune max. 7) Enable the drive. ADV200 WA • Functions description and parameters list...
  • Page 140 7608 (for PID 1) and 7658 (for PID 2) The above is also applicable to the PID 2 function, but points 2) and 3) are not necessary. The drive need not therefore be in “Local” mode. ADV200 WA • Functions description and parameters list...
  • Page 141 Menu Description Typo FB BIT 26.2.18 7638 PID 1 autotune RWZ VS Enabling of the autotuning procedure: if this parameter is set to 1 the PID 1 controller autotuning procedure is launched. ADV200 WA • Functions description and parameters list...
  • Page 142 ERW VS If the feedback signal does not reach maximum value par 7634 by the time limit configured with this param- eter, the PID output is reset and the autotuning procedure is completed. ADV200 WA • Functions description and parameters list...
  • Page 143: Process/Pid 2 References

    Set to 0 to select the value of reference signal 1 as the setpoint for the PID 2 function. Set to 1 to select the value of reference signal 2 as the setpoint for the PID 2 function. ADV200 WA • Functions description and parameters list...
  • Page 144 Selection of the operation to be executed on feedback signals 1 and 2 for the PID 2 controller: 0 Fbk1 1 Fbk2 2 Fbk1+Fbk2 3 Fbk1-Fbk2 4 Fbk1*Fbk2 5 Fbk1/Fbk2 6 Min fbk1fbk2 7 Max fbk1fbk2 ADV200 WA • Functions description and parameters list...
  • Page 145 26.3.15 7380 PID 2 process unit ENUM Use this parameter to select the unit of measure used in the process. 2 rpm 3 ppm 4 imp/s 5 l/s 6 l/m 7 l/h 8 kg/s 9 kg/m ADV200 WA • Functions description and parameters list...
  • Page 146 °C °F gal/s gal/m gal/h lb/s lb/m lb/h ft3/s ft3/m ft3/h ft/s in wg ft wg Lb/i2 ADV200 WA • Functions description and parameters list...
  • Page 147: Process/ Pid 2

    In this condition the drive reacts more quickly once the PID 2 controller output returns to within the limits. Menu Description Typo FB BIT 26.4.4 7656 PID 2 P gain FLOAT 16/32BIT 10.0 100.0 ADV200 WA • Functions description and parameters list...
  • Page 148 Menu Description Typo FB BIT 26.4.16 7684 PID 2 fbk tune thr 2 perc FLOAT 20.00 1.00 100.00 ERW VS ADV200 WA • Functions description and parameters list...
  • Page 149 ERW VS If the feedback signal does not reach maximum value par 7634 by the time limit configured with this param- eter, the PID output is reset and the autotuning procedure is completed. ADV200 WA • Functions description and parameters list...
  • Page 150: Process/Sleep Mode

    50 – 50*10% = 45 bar. This parameter is set to 0, the “Constant pressure” function is disabled. ADV200 WA • Functions description and parameters list...
  • Page 151 The pressure in the system is increased before stopping the motor to delay subsequent restarting. To obtain this effect, the reference is raised to a value set in this parameter for the time set in parameter 7460 Boost duration, before moving to the sleep condition. ADV200 WA • Functions description and parameters list...
  • Page 152 The drive status is displayed: a value of 1 indicates that the drive is in sleep mode. Displays pump Pause status: pump pause status can be displayed by means of a digital output selected from the L_DISEL1 list. ADV200 WA • Functions description and parameters list...
  • Page 153: Process/Flow Compens

    Setting of the pressure at the zero flow capacity point. This value depends on system characteristics. Menu Description Typo FB BIT 26.6.4 7506 FC design speed INT16 1000 CALCI Setting of the speed at the operating point. This value depends on system design characteristics. ADV200 WA • Functions description and parameters list...
  • Page 154 The compensated reference value output by the compensation block is displayed. This value is only calcu- lated if the flow compensation function is enabled. This parameter must be connected to the PID 1 reference source. ADV200 WA • Functions description and parameters list...
  • Page 155: Process/Fill

    Set to 0 to disable the fill function. Set to 1 to enable the fill function. Menu Description Typo FB BIT 26.7.2 7472 Fill speed INT16 CALCI Setting of the pump speed during horizontal pipe fill. ADV200 WA • Functions description and parameters list...
  • Page 156 PAR 7492 Fill enable src. In this way it could, for example via a digital input, fill a plant only the first time and skip the filling subsequent times when it is already full. ADV200 WA • Functions description and parameters list...
  • Page 157: Process/Min Frequency

    Setting of the speed to reach in the time set in parameter 7482 Freq min time. Menu Description Typo FB BIT 26.8.2 7482 Freq min time UINT16 3600 Setting of the time within which the minimum speed value set in parameter 7480 Freq min must be reached. ADV200 WA • Functions description and parameters list...
  • Page 158: Process/Check Valve

    Setting of the speed at which the ramp starts for the “check valve” function. Menu Description Typo FB BIT 26.9.4 7490 Check valve time UINT16 3600 Setting of the time it takes to pass from Check valve spd hi to Check valve spd low. ADV200 WA • Functions description and parameters list...
  • Page 159: Process/Pump Clean

    All the above conditions are independent and can be programmed separately. In case of timed startup, the time counter is reset if a cleaning cycle is started during the interval between one cycle and the next due to another source (startup, external event, analog measurement). ADV200 WA • Functions description and parameters list...
  • Page 160 Setting of the speed reference value for the normal direction of rotation during the pump cleaning function. Menu Description Typo FB BIT 26.10.8 7794 Clean rev speed INT16 CALCI Setting of the speed reference value for the reverse direction of rotation during the pump cleaning function. ADV200 WA • Functions description and parameters list...
  • Page 161 This parameter can be used to know whether a pump cleaning cycle is in progress and which command gen- erated it. 0 Not active 1 On start 2 Digital src 3 Analog src 4 Period src ADV200 WA • Functions description and parameters list...
  • Page 162: Process/Low Power Calc

    FB BIT 26.11.6 7750 Low pow correc fact perc FLOAT 100.0 200.0 Setting of the curve offset. This parameter can be used to correct the curve according to actual system condi- tions. ADV200 WA • Functions description and parameters list...
  • Page 163 FB BIT 26.11.7 7752 Low power mon FLOAT No flow The power calculated for the current speed is displayed. This value is used as the threshold for the and Dry pump alarms ADV200 WA • Functions description and parameters list...
  • Page 164 Menu Description Typo FB BIT 26.12.6 7850 Fire out mon 16BIT The status of the fire function is displayed. If this parameter is set to 1, the fire function is active. ADV200 WA • Functions description and parameters list...
  • Page 165: Process/Timers

    26.13.4 7866 TI 1 week day stop ENUM Sunday Setting of the day of the week on which TI 1 must stop. 0 Sunday 1 Monday 2 Tuesday 3 Wednesday 4 Thursday ADV200 WA • Functions description and parameters list...
  • Page 166 Setting of the hour in which TI 2 must stop. Menu Description Typo FB BIT 26.13.12 7882 TI 2 minute stop UINT16 Setting of the minute in which TI 2 must stop. ADV200 WA • Functions description and parameters list...
  • Page 167 26.13.19 7896 TI 4 week day start ENUM Sunday Setting of the day of the week on which TI 4 must start. 0 Sunday 1 Monday 2 Tuesday 3 Wednesday 4 Thursday 5 Friday 6 Saturday ADV200 WA • Functions description and parameters list...
  • Page 168 Typo FB BIT 26.13.27 7912 Timer1 status mon The timer 1 status is displayed: if set to 1, timer 1 is active. This timer 1 status may be connected to digital sources. ADV200 WA • Functions description and parameters list...
  • Page 169 The timer 3 status is displayed: if set to 1, timer 3 is active. This timer 3 status may be connected to digital sources. Menu Description Typo FB BIT 26.13.34 7926 Timer4 selection UINT16 2222 ADV200 WA • Functions description and parameters list...
  • Page 170 Typo FB BIT 26.13.36 7930 Timer4 status mon The timer 4 status is displayed: if set to 1, timer 4 is active. This timer 4 status may be connected to digital sources. ADV200 WA • Functions description and parameters list...
  • Page 171: Process/Multi Pump

    1418 Dig output 5X src = Pump 5 out mon 1420 Dig output 6X src = Pump 6 out mon 1422 Dig output 7X src = Pump 7 out mon 1424 Dig output 8X src = Pump 8 out mon ADV200 WA • Functions description and parameters list...
  • Page 172 1424 Dig output 8X src = Pump 4 lead mon When a “Pump X lead mon” output is active for a master pump, the equivalent “Pump X out mon” is deactivated, to avoid any damage to the inverter. ADV200 WA • Functions description and parameters list...
  • Page 173 Switching to another follower pump could result in temporary changes in pressure, causing other pumps to be acti- vated or deactivated. To avoid this, it is possible to override the bandwidth for a time that can be set in parameters Override time and Override bandwidth. ADV200 WA • Functions description and parameters list...
  • Page 174 7102 Staging bandwidth. Menu Description Typo FB BIT 26.14.5 7108 Override bandwidth perc INT16 Setting of the bandwidth of the follower pump used after switching a follower pump, to reduce the pressure ADV200 WA • Functions description and parameters list...
  • Page 175 26.14.13 7124 Alt actual time h.min UINT16 9999999 The time since the last alternation of the speed-controlled pump is displayed. Menu Description Typo FB BIT 26.14.14 7126 Altern ext event src LINK 16BIT 6000 16384 ADV200 WA • Functions description and parameters list...
  • Page 176 This signal must be connected to the digital output that controls the pump X control relay. ADV200 WA • Functions description and parameters list...
  • Page 177: Multidrive

    The first step is therefore to define whether each inverter is the controller or a follower by means of parameter 11348. The current system configuration calls for a single controller and a maximum of 7 followers. ADV200 WA • Functions description and parameters list...
  • Page 178 Specifically, if the Dig Out Opt Speed digital output is 1, the speed value transmitted by the controller is the optimal speed configured via parameter 11360 Optimal Speed; if the Dig Out Opt Speed digital output is 0, the speed value used by the drive is the Vref transmitted by the controller. ADV200 WA • Functions description and parameters list...
  • Page 179 You can initialize and reset the pump’s work hour counter by selecting the specific pump via parameters 11362, 11364, 11366. You can read the timer value via read-only parameters 12042 – 12056. ADV200 WA • Functions description and parameters list...
  • Page 180: Settings

    27.1.5 11354 Digital Maint Cmd Bool Use this parameter to enable pump maintenance status. To put pump X into maintenance, set the parameter of drive X to ON. 0 OFF 1 ON ADV200 WA • Functions description and parameters list...
  • Page 181 Use this parameter to select the pump for which you want to reset the work hour counter. 0 OFF (No pump selected) 1 Pompa 1 2 Pompa 2 3 Pompa 3 4 Pompa 4 5 Pompa 5 6 Pompa 6 7 Pompa 7 8 Pompa 8 ADV200 WA • Functions description and parameters list...
  • Page 182: I/O Controller

    Vref. 1800 AO1 (Analog Output 1) 1802 AO2 (Analog Output 2) 1850 AO1X (Analog Output 1 of the expansion I/O Card) 1852 AO2X (Analog Output 2 of the expansion I/O Card) ADV200 WA • Functions description and parameters list...
  • Page 183: Sequences

    27.3 SEQUENCES Menu Description Typo FB BIT 27.3.2 11402 Stage Threshold perc Float This is the speed threshold which, if exceeded, starts the pump with the fewest work hours (if work hours are ADV200 WA • Functions description and parameters list...
  • Page 184: I/O Follower

    DIG PAR 1110 DIE (Digital Input Enable) 1112 DI1 (Dig Inp 1) 1114 DI2 (Dig Inp 2) 1116 DI3 (Dig Inp 3) 1118 DI4 (Dig Inp 4) 1120 DI5 (Dig Inp 5) ADV200 WA • Functions description and parameters list...
  • Page 185 1310 DO1 (Digital Output 1) 1312 DO2 (Digital Output 2) 1314 DO3 (Digital Output 3) 1316 DO4 (Digital Output 4) 1410 DO1X (Digital Output 1 of the expansion I/O Card) ADV200 WA • Functions description and parameters list...
  • Page 186: Timer

    UDINT 27.5.6 12052 Pump 6 Timer UDINT 27.5.7 12054 Pump 7 Timer UDINT 27.5.8 12056 Pump 8 Timer UDINT Use this parameter to display the work hours of pump 2 ...8 (Follower). ADV200 WA • Functions description and parameters list...
  • Page 187: Macro

    Use this parameter to select a macro from the following list: 0 No Macro (Default). This selection do not set any Macro. 1 HVAC Standard 2 Supply Fan 3 Return Fan 4 Cooling Tower 5 Condenser 6 Booster Pump ADV200 WA • Functions description and parameters list...
  • Page 188: Hvac Standard

    (Relay 1) RS 485 (**) SMPS L1(*) (*): 1011 ... 61600: Integrated choke on DC link; ≥ 72000: external choke mandatory; (**) See ADV200 WA-QS manual, chapter 5.1.12, Connection of fans. Menu Description Typo FB BIT 27.1.1 11004 PID 1 ref 1 src...
  • Page 189 Selection of the operation to be executed on feedback signals 1 and 2 for the PID 1 controller: 0 Fbk1 1 Fbk2 2 Fbk1+Fbk2 3 Fbk1-Fbk2 4 Fbk1*Fbk2 5 Fbk1/Fbk2 6 Min fbk1fbk2 ADV200 WA • Functions description and parameters list...
  • Page 190 Setting of the integral gain of the PID 1 controller. Menu Description Typo FB BIT 27.2.9 11020 PID 1 I time FLOAT 3600.0 Setting of the integral time of the PID 1 controller. ADV200 WA • Functions description and parameters list...
  • Page 191: Supply Fan

    (Relay 1) RS 485 (**) SMPS L1(*) (*): 1011 ... 61600: Integrated choke on DC link; ≥ 72000: external choke mandatory; (**) See ADV200 WA-QS manual, chapter 5.1.12, Connection of fans. Menu Description Typo FB BIT 27.3.1 11052 PID 1 ref 1 src...
  • Page 192 Selection of the operation to be executed on feedback signals 1 and 2 for the PID 1 controller: 0 Fbk1 1 Fbk2 2 Fbk1+Fbk2 3 Fbk1-Fbk2 4 Fbk1*Fbk2 5 Fbk1/Fbk2 6 Min fbk1fbk2 ADV200 WA • Functions description and parameters list...
  • Page 193 Setting of the integral gain of the PID 1 controller. Menu Description Typo FB BIT 27.3.9 11072 PID 1 I time FLOAT 60.0 3600.0 Setting of the integral time of the PID 1 controller. ADV200 WA • Functions description and parameters list...
  • Page 194: Return Fan

    (Relay 1) RS 485 (**) SMPS L1(*) (*): 1011 ... 61600: Integrated choke on DC link; ≥ 72000: external choke mandatory; (**) See ADV200 WA-QS manual, chapter 5.1.12, Connection of fans. Menu Description Typo FB BIT 27.4.1 11102 PID 1 ref 1 src...
  • Page 195 Selection of the operation to be executed on feedback signals 1 and 2 for the PID 1 controller: 0 Fbk1 1 Fbk2 2 Fbk1+Fbk2 3 Fbk1-Fbk2 4 Fbk1*Fbk2 5 Fbk1/Fbk2 6 Min fbk1fbk2 ADV200 WA • Functions description and parameters list...
  • Page 196 Setting of the integral gain of the PID 1 controller. Menu Description Typo FB BIT 27.4.9 11118 PID 1 I time FLOAT 60.0 3600.0 Setting of the integral time of the PID 1 controller. ADV200 WA • Functions description and parameters list...
  • Page 197: Cooling Tower

    (Relay 1) RS 485 (**) SMPS L1(*) (*): 1011 ... 61600: Integrated choke on DC link; ≥ 72000: external choke mandatory; (**) See ADV200 WA-QS manual, chapter 5.1.12, Connection of fans. Menu Description Typo FB BIT 27.5.1 11152 PID 1 ref 1 src...
  • Page 198 Selection of the operation to be executed on feedback signals 1 and 2 for the PID 1 controller: 0 Fbk1 1 Fbk2 2 Fbk1+Fbk2 3 Fbk1-Fbk2 4 Fbk1*Fbk2 5 Fbk1/Fbk2 6 Min fbk1fbk2 ADV200 WA • Functions description and parameters list...
  • Page 199 Setting of the integral gain of the PID 1 controller. Menu Description Typo FB BIT 27.5.9 11172 PID 1 I time FLOAT 60.0 3600.0 Setting of the integral time of the PID 1 controller. ADV200 WA • Functions description and parameters list...
  • Page 200: Condenser

    (Relay 1) RS 485 (**) SMPS L1(*) (*): 1011 ... 61600: Integrated choke on DC link; ≥ 72000: external choke mandatory; (**) See ADV200 WA-QS manual, chapter 5.1.12, Connection of fans. Menu Description Typo FB BIT 27.6.1 11202 PID 1 ref 1 src...
  • Page 201 11214 PID 1 fbk function ENUM Fbk1 Selection of the operation to be executed on feedback signals 1 and 2 for the PID 1 controller: 0 Fbk1 1 Fbk2 2 Fbk1+Fbk2 3 Fbk1-Fbk2 ADV200 WA • Functions description and parameters list...
  • Page 202 Setting of the integral gain of the PID 1 controller. Menu Description Typo FB BIT 27.6.9 11218 PID 1 I time FLOAT 60.0 3600.0 Setting of the integral time of the PID 1 controller. ADV200 WA • Functions description and parameters list...
  • Page 203: Booster Pump

    (Relay 1) RS 485 (**) SMPS L1(*) (*): 1011 ... 61600: Integrated choke on DC link; ≥ 72000: external choke mandatory; (**) See ADV200 WA-QS manual, chapter 5.1.12, Connection of fans. Menu Description Typo FB BIT 27.7.1 11252 PID 1 ref 1 src...
  • Page 204 Selection of the operation to be executed on feedback signals 1 and 2 for the PID 1 controller: 0 Fbk1 1 Fbk2 2 Fbk1+Fbk2 3 Fbk1-Fbk2 4 Fbk1*Fbk2 5 Fbk1/Fbk2 6 Min fbk1fbk2 ADV200 WA • Functions description and parameters list...
  • Page 205 Setting of the integral gain of the PID 1 controller. Menu Description Typo FB BIT 27.7.9 11272 PID 1 I time FLOAT 60.0 3600.0 Setting of the integral time of the PID 1 controller. ADV200 WA • Functions description and parameters list...
  • Page 206: Parameters On Selection Lists, But Not Displayed On Keypad

    This signal is active when the reference is below the threshold set in parameter 940 Speed 0 threshold. The signal is activated after the delay set in parameter 942 Speed 0 delay. ADV200 WA • Functions description and parameters list...
  • Page 207 1060 Sequencer status UINT16 16 This signal indicates the state of the “machine states” that controls drive operation. STS_INIT STS_MAGN STS_STOP STS_START STS_FS_STOP STS_FS_START STS_QSTOP STS_FS_MAGN STS_W_QSTOP STS_READY STS_MAGN_START STS_ALM_DISABLED STS_ALM_END_ACTION 12 STS_ALM_STOP ADV200 WA • Functions description and parameters list...
  • Page 208 Menu Description Type FB BIT 1580 Analog inp2 This signal is active when the value of the analog input is below the threshold set in parameter 1570 Analog inp 2 thr. ADV200 WA • Functions description and parameters list...
  • Page 209 This parameter indicates the status of the Powerloss function 0 Powerloss not enabled 1 Powerloss enabled The function is enabled when there is a power failure. The function is disabled at different times depending on the Powerloss mode setting. ADV200 WA • Functions description and parameters list...
  • Page 210 This parameter displays the first alarm to be activated. 0 No alarm 1 Overvoltage 2 Undervoltage 3 Ground fault 4 Overcurrent 5 Desaturation 6 MultiUndervolt 7 MultiOvercurr 8 MultiDesat 9 Heatsink OT HeatsinkS OTUT ADV200 WA • Functions description and parameters list...
  • Page 211 1 = Undervoltage active 1 = Ground fault active 1 = Overcurrent active 1 = Desaturation active 1 – MultiUndervolt active 1 = MultiOvercurr active 1 – MultiDesat active 1 = Heatsink OT active ADV200 WA • Functions description and parameters list...
  • Page 212 This signal forces the variable to level one (always active). Menu Description Type FB BIT 6004 Speed limit state This signal is activated when the drive is in the speed limit condition. ADV200 WA • Functions description and parameters list...
  • Page 213 Menu Description Type FB BIT 6006 Current limit state This signal is activated when the drive is in the current limit condition. ADV200 WA • Functions description and parameters list...
  • Page 214: C - Parameter List (Expert)

    Time drive power on h.min UINT32 2.12 Time drive enable h.min UINT32 2.13 Number power up UINT16 2.14 Time fan on h.min UINT32 2.15 Power file ver.rel UINT16 2.16 Slot1 card type ENUM None None ADV200 WA • Parameters list (Expert)
  • Page 215 Regulation mode ENUM V/f control V/f control Flux vector OL Autotune Access mode ENUM Easy Easy Expert Control mode select ENUM Ramp ERWZ Torque Speed Ramp Application select ENUM None ERWZ None Application 1 ADV200 WA • Parameters list (Expert)
  • Page 216 Startup display INT16 20000 4.16 Display backlight 4.17 Language select ENUM English Italian French German Spanish Polish Romanian Russian Turkish Portuguese 4.18 Load default 4.19 Save par to keypad 4.20 Load par from keypad ADV200 WA • Parameters list (Expert)
  • Page 217 Acceleration time 2 FLOAT 10.0 0.01 1000.0 Deceleration time 2 FLOAT 10.0 0.01 1000.0 Acceleration time 3 FLOAT 10.0 0.01 1000.0 Deceleration time 3 FLOAT 10.0 0.01 1000.0 Ramp type ENUM Linear ERWZ Linear S-Shape Bypass ADV200 WA • Parameters list (Expert)
  • Page 218 Multi ref sel 2 src LINK 16BIT 6000 16384 L_DIGSEL2 7.22 Multi ref sel 3 src LINK 16BIT 6000 16384 L_DIGSEL2 7.23 Multi ref sel mon UINT16 7.24 Multi ref out mon INT16 16/32 0 8 - MOTORPOTENTIOMETER ADV200 WA • Parameters list (Expert)
  • Page 219 INT16 CALCI 10.2 Reference 0 delay UINT16 10000 10.3 Speed 0 thr INT16 CALCI 10.4 Speed 0 delay UINT16 10000 10.5 Speed threshold 1 INT32 CALCI CALCI 10.6 Speed threshold 2 INT32 CALCI CALCI ADV200 WA • Parameters list (Expert)
  • Page 220 1042 FR forward src LINK 16BIT 1112 16384 L_DIGSEL2 11.18 1044 FR reverse src LINK 16BIT 1114 16384 L_DIGSEL2 11.19 1046 FR *stop src LINK 16BIT 6000 16384 L_DIGSEL2 11.20 1048 FR start mon 16BIT 0 ADV200 WA • Parameters list (Expert)
  • Page 221 L_DIGSEL1 13.10 1412 Dig output 2X src LINK 16BIT 6000 16384 L_DIGSEL1 13.11 1414 Dig output 3X src LINK 16BIT 6000 16384 L_DIGSEL1 13.12 1416 Dig output 4X src LINK 16BIT 6000 16384 L_DIGSEL1 ADV200 WA • Parameters list (Expert)
  • Page 222 1560 Analog inp 2 filter FLOAT 10.0 1000.0 14.23 1562 Analog inp 2 top INT16 16384 -32768 +32767 14.24 1564 Analog inp 2 bottom INT16 -16384 -32768 +32767 14.25 1566 Analog inp 2 offset INT16 -32768 +32767 ADV200 WA • Parameters list (Expert)
  • Page 223 LINK 16/32 6000 16384 L_ANOUT 15.2 1802 Analog out 2 src LINK 16/32 6000 16384 L_ANOUT 15.3 1808 Analog out 1 scale FLOAT -10.0 10.0 15.4 1810 Analog out 2 scale FLOAT -10.0 10.0 ADV200 WA • Parameters list (Expert)
  • Page 224 1000.0 RWZS 16.5 2008 Pole pairs UINT16 SIZE RWZS 16.6 2010 Rated power FLOAT SIZE 1500.0 RWZS 16.7 2012 Rated power factor FLOAT SIZE 0.95 RWZS 16.8 2020 Take parameters 16.9 2022 Autotune rotation ADV200 WA • Parameters list (Expert)
  • Page 225 10000.0 ERWS 19.5 2264 Flux reg P gain OL A/Wb FLOAT CALCF ERWS 19.6 2266 Flux reg I time OL FLOAT CALCF 30000.0 ERWS 19.7 2270 Voltage reg P gain Wb/V FLOAT CALCF ERWS ADV200 WA • Parameters list (Expert)
  • Page 226 2490 Dig Vf scale FLOAT 16/32 1.0 ERWZ 21.23 2492 Vf scale src LINK 16/32 3374 16384 L_VREF 22 - FUNCTIONS 22.1 - FUNCTIONS/SPEED RATIO 22.1.1 3000 Dig speed ratio INT16 16/32 100 CALCI CALCI ADV200 WA • Parameters list (Expert)
  • Page 227 22.6 - FUNCTIONS/SPEED CAPTURE 22.6.1 3350 Speed capture ENUM Disable Disable Alarm restart Enable&restart 22.6.2 3364 Vf catch start freq FLOAT CALCF -500.0 500.0 ERWZ 22.6.3 3366 Vf catch enable dly UINT16 1000 10000 ERWZ ADV200 WA • Parameters list (Expert)
  • Page 228 3714 Pad 8 INT32 32BIT 0 22.9.9 3716 Pad 9 INT32 32BIT 0 22.9.10 3718 Pad 10 INT32 32BIT 0 22.9.11 3720 Pad 11 INT32 32BIT 0 22.9.12 3722 Pad 12 INT32 32BIT 0 ADV200 WA • Parameters list (Expert)
  • Page 229 UINT16 23.1.2 3802 Serial baudrate ENUM 38400 9600 19200 38400 23.1.3 3810 Serial parameter ENUM N_8_1 None,8,1 None,8,2 Even,8,1 Odd,8,1 23.1.4 3804 Serial protocol ENUM Modbus Modbus Jbus 23.1.5 3806 Serial delay UINT16 1000 ADV200 WA • Parameters list (Expert)
  • Page 230 Powerlink Profidrive 23.2.8 5608 IP address UINT32 4294967295 23.3 - COMMUNICATION/FIELDBUS M->S 23.3.1 4020 Fieldbus M->S1 ipa FBM2SIPA 20000 23.3.2 4022 Fieldbus M->S1 sys ENUM Not assigned 0 Not assigned Count 16 Count 32 ADV200 WA • Parameters list (Expert)
  • Page 231 Par 32 23.3.15 4054 Fieldbus M->S4 mon INT32 32BIT 0 23.3.16 4056 Fieldbus M->S4 div FLOAT 1000.0 23.3.17 4060 Fieldbus M->S5 ipa FBM2SIPA 20000 23.3.18 4062 Fieldbus M->S5 sys ENUM Not assigned 0 Not assigned ADV200 WA • Parameters list (Expert)
  • Page 232 Fill 32 Mdplc 16 Mdplc 32 Eu float Par 16 Par 32 23.3.31 4094 Fieldbus M->S8 mon INT32 32BIT 0 23.3.32 4096 Fieldbus M->S8 div FLOAT 1000.0 23.3.33 4100 Fieldbus M->S9 ipa FBM2SIPA 20000 ADV200 WA • Parameters list (Expert)
  • Page 233 Not assigned Count 16 Count 32 Fill 16 Fill 32 Mdplc 16 Mdplc 32 Eu float Par 16 Par 32 23.3.47 4134 Fieldbus M->S12 mon INT32 32BIT 0 23.3.48 4136 Fieldbus M->S12 div FLOAT 1000.0 ADV200 WA • Parameters list (Expert)
  • Page 234 23.3.62 4172 Fieldbus M->S16 sys ENUM Not assigned 0 Not assigned Count 16 Count 32 Fill 16 Fill 32 Mdplc 16 Mdplc 32 Eu float Par 16 Par 32 23.3.63 4174 Fieldbus M->S16 mon INT32 32BIT 0 ADV200 WA • Parameters list (Expert)
  • Page 235 23.4.12 4206 Fieldbus S->M3 mul FLOAT 1000.0 23.4.13 4210 Fieldbus S->M4 ipa FBS2MIPA 20000 23.4.14 4212 Fieldbus S->M4 sys ENUM Not assigned 0 Not assigned Count 16 Count 32 Fill 16 Fill 32 Mdplc 16 Mdplc 32 ADV200 WA • Parameters list (Expert)
  • Page 236 23.4.28 4246 Fieldbus S->M7 mul FLOAT 1000.0 23.4.29 4250 Fieldbus S->M8 ipa FBS2MIPA 20000 23.4.30 4252 Fieldbus S->M8 sys ENUM Not assigned 0 Not assigned Count 16 Count 32 Fill 16 Fill 32 Mdplc 16 ADV200 WA • Parameters list (Expert)
  • Page 237 INT32 32BIT 0 23.4.44 4286 Fieldbus S->M11 mul FLOAT 1000.0 23.4.45 4290 Fieldbus S->M12 ipa FBS2MIPA 20000 23.4.46 4292 Fieldbus S->M12 sys ENUM Not assigned 0 Not assigned Count 16 Count 32 Fill 16 ADV200 WA • Parameters list (Expert)
  • Page 238 23.4.59 4324 Dig Fieldbus S->M15 INT32 32BIT 0 23.4.60 4326 Fieldbus S->M15 mul FLOAT 1000.0 23.4.61 4330 Fieldbus S->M16 ipa FBS2MIPA 20000 23.4.62 4332 Fieldbus S->M16 sys ENUM Not assigned 0 Not assigned Count 16 ADV200 WA • Parameters list (Expert)
  • Page 239 4452 Word decomp src LINK 16BIT 4450 16384 L_WDECOMP 23.6.3 4454 Bit0 decomp mon 16BIT 0 23.6.4 4456 Bit1 decomp mon 16BIT 0 23.6.5 4458 Bit2 decomp mon 16BIT 0 23.6.6 4460 Bit3 decomp mon 16BIT 0 ADV200 WA • Parameters list (Expert)
  • Page 240 PT100 AN1X PT100 AN2X KTY84 24.13 4532 MotorOT thr UINT16 32767 24.14 4536 MotorOT mon INT16 32767 24.15 4540 Overspeed threshold INT32 CALCI CALCI 24.16 4542 Overspeed activity ENUM Disable Ignore Warning Disable Stop ADV200 WA • Parameters list (Expert)
  • Page 241 24.33 4622 IOverC restart time UINT16 2000 1000 10000 24.34 4630 OverV restart ENUM Disable Disable Enable 24.35 4632 OverV restart time UINT16 2000 1000 10000 24.36 4640 UnderV restart ENUM Enable Disable Enable ADV200 WA • Parameters list (Expert)
  • Page 242 External fault Not Used2 Overspeed Speed ref loss Emg stop alarm Power down Broken belt End curve Dry pump No flow Clean alarm Not Used6 Plc1 fault Plc2 fault Plc3 fault Plc4 fault Plc5 fault ADV200 WA • Parameters list (Expert)
  • Page 243 Plc8 fault 24.48 4704 Alarm dig sel 3 ENUM No alarm No alarm Overvoltage Undervoltage Ground fault Overcurrent Desaturation MultiUndervolt MultiOvercurr MultiDesat Heatsink OT HeatsinkS OTUT Intakeair OT Motor OT Drive overload Motor overload ADV200 WA • Parameters list (Expert)
  • Page 244 Opt 1 IO fault Opt 2 IO fault Not Used1 External fault Not Used2 Overspeed Speed ref loss Emg stop alarm Power down Broken belt End curve Dry pump No flow Clean alarm Not Used6 Plc1 fault ADV200 WA • Parameters list (Expert)
  • Page 245 Stop Fast stop 24.66 7816 Analog 1 err act ENUM Ignore Ignore Warning Disable Stop Fast stop 24.67 7818 Analog 1 err delay FLOAT 24.68 7820 Analog 2 err act ENUM Ignore Ignore Warning ADV200 WA • Parameters list (Expert)
  • Page 246 26.1.11 7322 PID 1 fbk 2 src LINK 16/32 6000 16384 L_PIDFBK 26.1.12 7324 PID 1 fbk function ENUM Fbk1 Fbk1 Fbk2 Fbk1+fbk2 Fbk1-fbk2 Fbk1*fbk2 Fbk1/fbk2 Min fbk1fbk2 Max fbk1 fbk2 Aver fbk1 fbk2 2 Zone min ADV200 WA • Parameters list (Expert)
  • Page 247 Disable Enable 26.2.4 7606 PID 1 P gain FLOAT 10.0 100.0 26.2.5 7608 PID 1 I time FLOAT 60.0 3600.0 26.2.6 7610 PID 1 D time FLOAT 26.2.7 7614 PID 1 filter FLOAT 10.0 ADV200 WA • Parameters list (Expert)
  • Page 248 Aver fbk1 fbk2 2 Zone min 2 Zone max 26.3.13 7386 PID 2 fbk filter FLOAT 10.0 26.3.14 7376 PID 2 fbk out mon PID2U FLOAT 26.3.15 7380 PID 2 process unit ENUM perc imp/s ADV200 WA • Parameters list (Expert)
  • Page 249 INT16 16/32 0 26.4.13 7678 PID 2 fbk tune min PID2U FLOAT 26.4.14 7680 PID 2 fbk tune max PID2U FLOAT 100.0 26.4.15 7682 PID 2 fbk tune thr 1 perc FLOAT 0.10 0.00 ADV200 WA • Parameters list (Expert)
  • Page 250 7492 Fill enable src LINK 16BIT 7470 16384 26.8 - PROCESS/MIN FREQUENCY 26.8.1 7480 Freq min INT16 CALCI 26.8.2 7482 Freq min time UINT16 3600 26.9 - PROCESS/CHECK VALVE 26.9.1 7484 Check valve enable ENUM Disable ADV200 WA • Parameters list (Expert)
  • Page 251 26.11.7 7752 Low power mon FLOAT 26.12 - PROCESS/FIRE FUNCTION 26.12.1 7840 Fire function ENUM Disable Disable Forward Reverse Forward bypass 26.12.2 7842 Fire command src LINK 16BIT 6000 16384 L_DIGSEL2 26.12.3 7844 Fire speed INT16 CALCI ADV200 WA • Parameters list (Expert)
  • Page 252 26.13.13 7884 TI 3 week day start ENUM Sunday Sunday Monday Tuesday Wednesday Thursday Friday Saturday 26.13.14 7886 TI 3 hour start UINT16 26.13.15 7888 TI 3 minute start UINT16 26.13.16 7890 TI 3 week day stop ENUM Sunday Sunday ADV200 WA • Parameters list (Expert)
  • Page 253 26.14.6 7110 Override time UINT16 3600 26.14.7 7112 Staging speed perc INT16 26.14.8 7114 Destaging speed perc INT16 26.14.9 7116 Destage time UINT16 3600 26.14.10 7118 Pumps cycle 26.14.11 7120 Alternation mode ENUM Disable ADV200 WA • Parameters list (Expert)
  • Page 254 11356 Maintenance Cmd Sel ENUM 27.1.7 11358 Auto Setup Bool 27.1.8 11360 Opt Speed Perc 27.1.9 11362 Pump Time Reset Sel Enum 27.1.10 11364 Pump Set Time Enum 27.1.11 11366 Pump Time Reset Cmd Bool ADV200 WA • Parameters list (Expert)
  • Page 255 12046 Pump 3 Timer UDINT 27.5.4 12048 Pump 4 Timer UDINT 27.5.5 12050 Pump 5 Timer UDINT 27.5.6 12052 Pump 6 Timer UDINT 27.5.7 12054 Pump 7 Timer UDINT 27.5.8 12056 Pump 8 Timer UDINT ADV200 WA • Parameters list (Expert)
  • Page 256 16384 27.3.5 11062 PID 1 fbk 1 src LINK 16/32 1500 16384 27.3.6 11064 PID 1 fbk 2 src LINK 16/32 0 16384 27.3.7 11068 PID 1 fbk function ENUM Fbk1 Fbk1 Fbk2 Fbk1+Fbk2 ADV200 WA • Parameters list (Expert)
  • Page 257 27.5.5 11162 PID 1 fbk 1 src LINK 16/32 1500 16384 27.5.6 11164 PID 1 fbk 2 src LINK 16/32 0 16384 27.5.7 11168 PID 1 fbk function ENUM Fbk1 Fbk1 Fbk2 Fbk1+Fbk2 Fbk1-Fbk2 ADV200 WA • Parameters list (Expert)
  • Page 258 27.7.5 11262 PID 1 fbk 1 src LINK 16/32 1500 16384 27.7.6 11264 PID 1 fbk 2 src LINK 16/32 0 16384 27.7.7 11268 PID 1 fbk function ENUM Fbk1 Fbk1 Fbk2 Fbk1+Fbk2 Fbk1-Fbk2 ADV200 WA • Parameters list (Expert)
  • Page 259 28.4.6 Slot3 card S/N UINT32 28.5 - SERVICE/PID AUTOTUNING 28.5.1 8100 PID 1 sys T const FLOAT 28.5.2 8102 PID 1 sys K gain FLOAT 0.01 28.5.3 8104 PID 1 sys delay FLOAT 10.0 ADV200 WA • Parameters list (Expert)
  • Page 260 1114 Digital input 2 mon 16BIT 0 1116 Digital input 3 mon 16BIT 0 1118 Digital input 4 mon 16BIT 0 1120 Digital input 5 mon 16BIT 0 1210 Digital input 1X mon 16BIT 0 ADV200 WA • Parameters list (Expert)
  • Page 261 4840 Alarm lo state UINT32 32BIT 0 4842 Alarm hi state UINT32 32BIT 0 6000 Null UINT32 32BIT 0 6002 One UINT32 32BIT 1 6004 Speed limit state 16BIT 0 6006 Current limit state 16BIT 0 ADV200 WA • Parameters list (Expert)
  • Page 262: D - Selection Lists

    4714 Alm dig out mon 4 3718 Pad 10 22.9.10 3712 Pad 7 22.9.7 1530 Analog inp1<thr 3720 Pad 11 22.9.11 3714 Pad 8 22.9.8 1580 Analog inp2<thr 3722 Pad 12 22.9.12 3716 Pad 9 22.9.9 Drive overload trip ADV200 WA • Selection lists...
  • Page 263: L_Digsel2

    4464 Bit5 decomp mon 23.6.8 7182 Pump 7 lead mon 26.14.38 1048 FR start mon 11.20 4466 Bit6 decomp mon 23.6.9 7184 Pump 8 lead mon 26.14.39 1050 FR reverse mon 11.21 4468 Bit7 decomp mon 23.6.10 ADV200 WA • Selection lists...
  • Page 264: L_Digsel4

    3708 Pad 5 22.9.5 3718 Pad 10 22.9.10 1064 Drive ready 3710 Pad 6 22.9.6 3720 Pad 11 22.9.11 3712 Pad 7 22.9.7 3722 Pad 12 22.9.12 3714 Pad 8 22.9.8 3724 Pad 13 22.9.13 ADV200 WA • Selection lists...
  • Page 265: L_Mltref

    1600 Analog input 1X mon 14.33 (4) = 604 Dig ramp ref 3 4044 Fieldbus M->S3 mon 23.3.11 1650 Analog input 2X mon 14.44 4054 Fieldbus M->S4 mon 23.3.15 7520 FC ref out mon 26.6.11 ADV200 WA • Selection lists...
  • Page 266: L_Scope

    3714 Pad 8 22.9.8 4154 Fieldbus M->S14 mon 23.3.55 3716 Pad 9 22.9.9 4164 Fieldbus M->S15 mon 23.3.59 3718 Pad 10 22.9.10 4174 Fieldbus M->S16 mon 23.3.63 3720 Pad 11 22.9.11 3700 Pad 1 22.9.1 ADV200 WA • Selection lists...
  • Page 267: E - Troubleshooting - Alarms

    - Verify the correct operation of the cooling fan. - Check that the heatsinks are not clogged - Check that the openings for the cabinet cooling air are not blocked. Intakeair OT Condition: Intake air temperature too high alarm. Solution: Check correct fan operation ADV200 WA • Troubleshooting...
  • Page 268 100 rpm. This condition occurs because the drive is in the current limit condition. It is only available in the Flux Vect OL mode. Solution: Check the drive load conditions ADV200 WA • Troubleshooting...
  • Page 269 Analog 2 Err = Error on analog channel 2 Analog 3 Err = Error on analog channel 1 of expansion card Analog 4 Err = Error on analog channel 2 of expansion card Solution: Check connections. ADV200 WA • Troubleshooting...
  • Page 270: F - Messages

    Solution: Close the enable contact before sending the Autotune command A setting performed by Autotune has reached a measurement method limit 8 ... 21 Solution: Check the motor plate data or the drive and motor sizes have been combined incor- rectly. ADV200 WA • Troubleshooting...
  • Page 271 Non-permissible optional card in slot 1 0002H-2 Non-permissible optional card in slot 2 0004H-4 Non-permissible optional card in slot 3 0010H-16 Conflict slot 1 with slot 2 0020H-32 Conflict slot 1 with slot 3 0040H-64 Conflict slot 2 with slot 3 ADV200 WA • Troubleshooting...
  • Page 272 Incorrect PLC key. PLC application not available. Solution: Ask Gefran to supply the correct key to enable the desired firmware function. Condition: this may occur at drive power-on if the incorrect enabling key was inserted for a given firmware function.
  • Page 273 Solution: Check the hardware configuration, then press ESC. Save the parameters (Save parameters, menu 04.1 par 550) to save the new hardware configuration. Note! For any messages that are displayed but not included in this list reference should be made to the manual for the application used by the drive. ADV200 WA • Troubleshooting...
  • Page 274: G - Block Diagrams

    G - Block Diagrams System Diagrams Index Drive overview ADV200 WA • Block Diagrams...
  • Page 275: References

    References ADV200 WA • Block Diagrams...
  • Page 276: Ramps

    Ramps Multireference ADV200 WA • Block Diagrams...
  • Page 277: Motorpotentiometer

    Motorpotentiometer Jog function ADV200 WA • Block Diagrams...
  • Page 278: Monitor Function

    Monitor function ADV200 WA • Block Diagrams...
  • Page 279 ADV200 WA • Block Diagrams...
  • Page 280: Commands

    Commands ADV200 WA • Block Diagrams...
  • Page 281 ADV200 WA • Block Diagrams...
  • Page 282: Digital Inputs

    Digital inputs ADV200 WA • Block Diagrams...
  • Page 283: Digital Outputs

    Digital outputs ADV200 WA • Block Diagrams...
  • Page 284: Analog Inputs

    Analog inputs ADV200 WA • Block Diagrams...
  • Page 285 ADV200 WA • Block Diagrams...
  • Page 286: Analog Outputs

    Analog outputs ADV200 WA • Block Diagrams...
  • Page 287: Speed Reg Gains

    Speed reg gains ADV200 WA • Block Diagrams...
  • Page 288: Vf Parameters

    VF parameters ADV200 WA • Block Diagrams...
  • Page 289: Functions

    Functions ADV200 WA • Block Diagrams...
  • Page 290 ADV200 WA • Block Diagrams...
  • Page 291 ADV200 WA • Block Diagrams...
  • Page 292 ADV200 WA • Block Diagrams...
  • Page 293: Process

    Process ADV200 WA • Block Diagrams...