7.2
Transient Transmission Program
This section describes the procedure for creating a program using transient transmission.
System configuration example
For details on the system configuration, refer to the following.
Page 29 System configuration
Setting in the control station
For details on how to set parameters for the control station, refer to the following.
Page 31 Setting in the control station
Setting in the normal stations
For details on how to set parameters for the normal stations, refer to the following.
Page 34 Setting in the normal stations
Checking the network status
For details on how to check the network status, refer to the following.
Page 36 Checking the network status
Program example
Program example of transient transmission
The following shows a program example of transient transmission.
■Overview of the program example
Through transient transmission, by using the READ instruction, the values in D300 to D304 of the normal station (station
No.2) are read to D800 to D804 of the control station (station No.1).
When creating a program, configure an interlock using 'Baton pass error status of own station' (SB0047) and 'Baton pass
status of each station' (SW0070 to SW0073).
Classification
Module label
Label to be defined
7 COMMUNICATION EXAMPLES
40
7.2 Transient Transmission Program
Label name
LP21_1.bDetect_BatonPassError
LP21_1.bnSts_BatonPassError_Station[1]
Define global labels as shown below:
Description
Baton pass error status of own
station
Baton pass status of each
station
Device
SB0047
SW0070 to SW0073