Setting The Module; Initializing The C Controller Module - Mitsubishi Electric MELSEC iQ-R Series Quick Start Manual

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

2.3

Setting the Module

Initializing the C Controller module

Check that the RESET/STOP/RUN switch is positioned at the center at first.
(2)
(2)
(5)
(2)
(4)
(5)
2 USING C CONTROLLER MODULE
10
2.3 Setting the Module
(1)
(1)
(3)
(2)
1.
Put and hold the MODE/SELECT switch (1) on the
MODE position.
2.
Turn the power of the C Controller module ON. The
BUS RUN LED (2) turns ON, and "M-00" is displayed on
the dot matrix LED.
3.
Release the MODE/SELECT switch (1) and put it back
to the center position.
4.
Set the MODE/SELECT switch (1) to the SELECT
position. Every time the switch is set to the SELECT
position, the value of mode displayed on the dot matrix
LED is changed. Repeat this switch movement until
"0011" is displayed on the dot matrix LED.
5.
Set the RESET/STOP/RUN switch (3) to the RUN
position. The selected mode is executed. The BUS RUN
LED (2) will be flashing during initialization.
6.
Check that the BUS RUN LED (2) turns ON and "0000"
is displayed on the dot matrix LED, then reset the C
Controller module. For the reset procedure, refer to the
following section.
(Page 11 Resetting procedure)
7.
The initialization is performed by resetting the module.
The READY LED (5) will turn ON, and the BUS RUN
LED (2) and USER LED (4) will be flashing during the
initialization.
8.
Upon normal completion of the initialization, the BUS
RUN LED (2) and USER LED (4) turns OFF, and the
READY LED (5) starts flashing.
9.
Reset the C Controller module. For the procedure, refer
to the following section.
(Page 11 Resetting procedure)

Advertisement