7 MAINTENANCE
7.3.3 Communication error codes
When a parameter setting error or communication error is detected, the associated information is
stored in the error code section (BD000) of the status area within the BD register. The error
codes are listed below:
No.
Error name
1
Control register setting error
2
Communication response wait time setting
error
3
Communication retry count setting error
4
Cyclic communication protocol setting error
5
Remote station IP address setting error
6
Endian conversion setting error
7
Module number setting error
8
Local station transmission/reception start
address setting error
9
Remote station transmission/reception start
address setting error
10
Bit/word mismatch error
11
Transmission/reception data size setting error
12
Port opening error
13
Port closing error
14
Cyclic communication data transmission error
15
Cyclic communication data reception error
16
Cyclic communication timeout error
17
Cyclic communication data size error
18
Cyclic communication response error
List of SV.LINK module internal error codes (which are the "Hxxxx" portion in the above error
code table)
Error code
Description
0xFFF0
Address error
Network error
Cause
A transmission was directed to
the local station's IP address.
An Ethernet-level error (e.g.,
collision) occurred during a
transmission.
The cable was disconnected.
Error code
High-order
Low-order
word
word
H1100
H0000
H1101
H0000
H1102
H0000
H1103
H0000
H1104
H0000
H1105
H0000
H1106
H0000
H1107
H0000
H1108
H0000
H1109
H0000
H110A
H0000
H1200
Hxxxx
H1201
Hxxxx
H2301
Hxxxx
H2302
Hxxxx
H2303
H0000
H2304
H0000
H2305
H0000
Review the IP address specified for the remote station
(BD00D of the BD register) and perform setup again.
Check the connectors, cable, and remote station for
abnormalities. Also, check the wiring to ensure that
the cable is not affected by noise.
Check that the cable is properly connected to the
connectors.
7-12
Remedy
A parameter setting was in error.
See "5.4 Status and
Communication Parameter Areas,"
and correct the communication
parameter setting. Then perform a
reset or power-on reset.
See the table below and take an
appropriate remedial action. If the
error recurs later, replace the
SV.LINK module. The "xxxx"
portion represents an internal error
code. For the meanings of internal
error codes, see the table below.
The MELSEC was stopped or the
preselected wait time (BD009) was
too short. Correct the setting.
The S10mini or S10V and MELSEC
did not agree in word count.
Correct the setting.
An improper method was employed
for communications. Review the
user program on the MELSEC side.
Remedy