The device type is "0009" for the digitalYEWFLO.
The software name is "ORIGINAL" or "UPDATE."
The former indicates an original file and the latter
an update file. Whenever performing a download to
update the device revision, obtain the original file.
In general, an addition to the parameters or blocks
requires a device revision update.
A11.6 Steps after Activating a
Field Device
When the communication with a field device has
recovered after activating the device, check using
the download tool that the software revision of the
field device has been updated accordingly. The
value of SOFT_REV of the resource block indicates
the software revision.
The PD tag, node address, and transducer block
calibration parameters that are retained in the
nonvolatile memory inside the target device will
remain unchanged after a software download.
However, after a software update which causes an
addition to the block parameters or blocks, or to the
system/network management VFD parameters,
some parameters may be reset to the defaults, thus
requiring parameter setup and engineering again.
For details, read Table A11.1.
Also note that a change in the number of
parameters or blocks requires the DD and
capabilities files corresponding to the new software
revision.
Table A11.1 Actions after Software Update
Contents of Software Update
Does not change the number
of parameters.
Adds a block parameter.
Adds a block.
Changes the number of
system/network management
VFD parameters.
<APPENDIX 11. SOFTWARE DOWNLOAD (Option /EE)>
Action
Re-setup of parameters not
needed.
Setup of the added parameter
needed.
Reengineering and setup of
the added block's parameters
needed.
Reengineering needed.