8.

DEVICE STATUS

In a digitalYEWFLO, the current device statuses
and error details are represented by parameters
DEVICE_STATUS_1 to DEVICE_STATUS_5
(indexes 1045 to 1049) inside the resource
statuses.
Table 8.1
Contents of DEVICE_STATUS_1 (Index 1045)
Hexadecimal
Display through DD
0x04000000 Abnormal boot process
0x02000000 Download failure
0x01000000 Download incomplete
0x00800000 Simulate enable jumper On
0x00400000 RB in O/S mode (AL-21)
0x00080000 AMP. module failure 2 (AL-04)
0x00008000 Link Obj.1/17/33 not open
0x00004000 Link Obj.2/18/34 not open
0x00002000 Link Obj.3/19/35 not open
0x00001000 Link Obj.4/20/36 not open
0x00000800 Link Obj.5/21/37 not open
0x00000400 Link Obj.6/22/38 not open
0x00000200 Link Obj.7/23/39 not open
0x00000100 Link Obj.8/24/40 not open
0x00000080 Link Obj.9/25 not open
0x00000040 Link Obj.10/26 not open
0x00000020 Link Obj.11/27 not open
0x00000010 Link Obj.12/28 not open
0x00000008 Link Obj.13/29 not open
0x00000004 Link Obj.14/30 not open
0x00000002 Link Obj.15/31 not open
0x00000001 Link Obj.16/32 not open
Table 8.2
Contents of DEVICE_STATUS_2 (Index 1046)
Hexadecimal
Display through DD
0x00000040 Temp. sensor failure (AL-08)
0x00000020 Temp. converter failure (AL-07)
0x00000010 Input circuit failure (AL-06)
0x00000008 Flow sensor failure (AL-05)
0x00000004 COM. circuit failure 2 (AL-03)
0x00000002 COM. circuit failure 1 (AL-02)
0x00000001 AMP. module failure 1 (AL-01)
Abnormal boot processing was detected at the time of starting.
Software download failed.
Software download is incomplete.
The SIMULATE_ENABLE switch is ON.
The resource block is in O/S mode.
The EEPROM (F) is faulty.
The VCR selected in link object is not open.
The VCR selected in link object is not open.
The VCR selected in link object is not open.
The VCR selected in link object is not open.
The VCR selected in link object is not open.
The VCR selected in link object is not open.
The VCR selected in link object is not open.
The VCR selected in link object is not open.
The VCR selected in Link object is not open.
The VCR selected in Link object is not open.
The VCR selected in Link object is not open.
The VCR selected in Link object is not open.
The VCR selected in Link object is not open.
The VCR selected in Link object is not open.
The VCR selected in Link object is not open.
The VCR selected in Link object is not open.
The temperature sensor is faulty.
The temperature circuit in the amplifier is faulty.
The input circuit is in the amplifier is faulty.
The flow sensor is faulty.
The fieldbus communication circuit in the amplifier is faulty (type 2 error).
The fieldbus communication circuit in the amplifier is faulty (type 1 error).
The EEPROM (S) is faulty.
<8. DEVICE STATUS>
Description
Description
8-1
IM 01F06F00-01EN