INSTALLATION
2.5

DEVICENET CONNECTIONS AND SETUP

2.5.1
DeviceNet Node Address (MAC ID) and Baud Rate
Selection
To interface the C-BOX 4X0 with a DeviceNet network, the Node Address (MAC ID)
and the baud rate should be set using the rotary switches placed in the cover inside.
The valid address range for the Node Address (MAC ID) is from 00 to 63.
If an invalid value is detected (64-99), the C-BOX cannot communicate with the
DeviceNet network and the red LED (MS LEDs) is turned on. The MAC ID value 99 is
reserved.
The Node Address can also be assigned through WinHost. Refer to Help on-Line.
The valid range for the baud rate selection is:
-
0 = 125 Kb per second
-
1 = 250 Kb per second
-
2 = 500 Kb per second
If an invalid value is detected (3-9), the C-BOX 4X0 cannot communicate with the
DeviceNet network and the red LED (MS LEDs) is turned on.
2.5.2
DeviceNet Connector (M12 Male External Sealed Micro
Connector)
To connect C-BOX 4X0 as a DeviceNet node, use a standard DeviceNet cable with
an M12 female connector and plug it into the M12 male external connector.
MAC ID
Baud Rate
Figure 11 - Rotary Switches