Daikin Destiny VFD Series Installation And Maintenance Manual page 18

Indoor air handler
Table of Contents

Advertisement

Heater Amps
Table 3: Heater Amps
KW
1
1.5
2
2.5
3
3.5
4
4.5
5
5.5
6
6.5
7
7.5
8
8.5
9
10
11
12
13
14
15
16
17
18
19
20
22
24
26
28
30
32
34
36
38
40
45
50
55
Electric Heat Safety
Overcurrent Protection
Overcurrent fuse protection is provided for each stage of
electric heat (in lieu of one per 48 amperes).
Thermal (Over Temperature) Protection
Primary - Automatic limit switches, one per step (120°F or
150°F as appropriate).
Backup - Manual reset thermal cutout (180°F).
IM 782-12 • DESTINY AIR HANDLERS
120V / 1Ø
240V / 1Ø
8.33
4.17
12.50
6.25
16.67
8.33
20.83
10.42
25.00
12.50
29.17
14.58
33.33
16.67
37.50
18.75
41.67
20.83
45.83
22.92
50.00
25.00
54.17
27.08
58.33
29.17
62.50
31.25
66.67
33.33
70.83
35.42
75.00
37.50
83.33
41.67
91.67
45.83
100.00
50.00
108.33
54.17
116.67
58.33
125.00
62.50
133.33
66.67
141.67
70.83
150.00
75.00
158.33
79.17
N/A
83.33
N/A
91.67
N/A
100.00
N/A
108.33
N/A
116.67
N/A
125.00
N/A
133.33
N/A
141.67
N/A
150.00
N/A
158.33
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Heater Amps
240V / 3Ø
2.41
3.61
4.82
6.02
7.23
8.43
9.63
10.84
12.04
13.25
14.45
15.66
16.86
18.06
19.27
20.47
21.68
24.08
26.49
28.90
31.31
33.72
36.13
38.54
40.94
43.35
45.76
48.17
52.99
57.80
62.62
67.44
72.25
77.07
81.89
86.71
91.52
96.34
108.38
120.42
132.47
Fan Interlock Method:
To prevent the heater from being energized unless the fan
is on, the heater includes two interlock methods: an airflow
switch, and the use of an auxiliary contact in the motor starter
contactor (3ph) or a fan relay (1ph).
Airflow Switch:
The airflow switch provides the best means of protection against
air failure caused by fan belt or other malfunction. Switches are
of the differential pressure, diaphragm-operated type and require
a minimum total pressure differential of .05" WC. The switch is
factory wired in series with the manual reset cutout.
18
Installation
480V / 3Ø
600V / 3Ø
1.20
0.96
1.81
1.45
2.41
1.93
3.01
2.41
3.61
2.89
4.21
3.37
4.82
3.85
5.42
4.34
6.02
4.82
6.62
5.30
7.23
5.78
7.83
6.26
8.43
6.74
9.03
7.23
9.63
7.71
10.24
8.19
10.84
8.67
12.04
9.63
13.25
10.60
14.45
11.56
15.66
12.52
16.86
13.49
18.06
14.45
19.27
15.41
20.47
16.38
21.68
17.34
22.88
18.30
24.08
19.27
26.49
21.19
28.90
23.12
31.31
25.05
33.72
26.97
36.13
28.90
38.54
30.83
40.94
32.76
43.35
34.68
45.76
36.61
48.17
38.54
54.19
43.35
60.21
48.17
66.23
52.99
www.DaikinApplied.com