Daikin Destiny VFD Series Installation And Maintenance Manual page 11

Indoor air handler
Table of Contents

Advertisement

Figure 11: Reversing the Coil Handing
1
Remove screws
from the upper track
that hold coil/drain pan
in place
Airflow
3
Remove screws and
remove coil blockoffs.
5
Rotate coil 180°
and reposition in
drain pan.
All coils
except DX
NOTE:
Rotate a DX
(evaporator)
coil 180° TOP
to BOTTOM.
Airflow
www.DaikinApplied.com
2
Lift drain pan connection
up and slide coil/drain pan
assembly out.
4
Remove screws
holding coil to
drain pan and
remove coil.
6
Drill holes in coil
bottom flange
and install screws
to secure to
drain pan.
Airflow
Distributors
must be on the
leaving air side
of the coil.
8
Mark locations
and drill holes
to align with holes
in upper track.
9
NOTE:
If a heating coil
is used, position
heating coil on
the leaving
side of the
cooling coil.
11
Installation
7
Drill holes in coil header plate
flanges, position block offs
and install screws to secure to coil.
Position coil/drain pan
assembly in unit and install
screws in upper track.
IM 782-12 • DESTINY AIR HANDLERS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents