Electric Heat Section

(Optional)
Optional factory installed electric heat section consists of
open coil duct heater mounted to the unit at the supply fan
discharge. Heat section includes heating coils and an electrical
control box with single point field power connection for heater
and supply air fan.
Factory provided field knockouts are located on the side
of the electric heat control panel for field power and
control wiring to pass through. A factory installed non-
fused disconnect is located in the electric heat control
panel to disconnect power to the supply air fan and heater
components. All wiring must be in conformance with the
national electric code and local restrictions.
Open Coil Duct Heater
• Complete with overload and thermal protection
• Includes fan interlock and air flow switch safety protection
• High quality, alloy nichrome wire [80%Ni / 20%Cr]
• High di-electric level ceramic insulators
• Screw terminals
Single Point Power
• Non-fused disconnect
• Electric heat is factory wired including contactors and
fuses per step and as required by UL. Refer to
Heat Diagrams on page 23
wiring diagrams
• Fan motor is factory wired including contactor or starter
and fuses as applicable
• Fused control transformer allows the heater and fan to be
sequenced by standard 24 volt thermostat
• Indoor control panel with tool access hinged door houses
all components
Quality Control
• Heaters are di-electrically tested for 1000V plus twice the
rated volts, or 2000V whichever is greater. The resistance
of each heater is measured and recorded and must be
within 5% of the rated value
• Every heater is checked during the production process
and as a final assembly
www.DaikinApplied.com
Electric
for typical electric heat
Figure 23: Heater Nomenclature
C M XX - XX - X X
Heater
Modular
Voltage
Figure 24: Destiny Unit with Left Hand Electric Heat
Knockouts: Four Diameters
2.38, 1.62, 1.88, 1.00
Left Hand Electric
Heat Shown
(Right Hand Optional)
f l o w
A i r
Electric Heat Matches
Destiny Fan Discharge
and Attaches Directly
to Destiny Unit
Electric Heat kW Options
Table 2: KW Options by Unit Size
002
003
KW
1.5–10
2.5–20
Range
17
Installation
2.25
3.00
3.00
Removable Panel
for Full Access
9.50
Unit Size
004
005
007
2.5–20
4–26
6–38
IM 782-12 • DESTINY AIR HANDLERS
Steps
Phases
Wattage
010
6–55