Power Circuits And Bar Connections; Busbar Connection Recommandations - socomec ATyS d H Instruction Manual

Remotely operated transfer switching equipment
Hide thumbs Also See for ATyS d H:
Table of Contents

Advertisement

IEC
GB
60947-6-1
14048.11
AC-32B
AC-33iB
PC
PC
660 V 50/60 Hz
660 V 50 Hz
4000 A
4000 A
143 kA
143 kA
65 kA / 0.1s
65 kA / 0.1s
12 kV
12 kV
65 A
65 A

5.4. Power circuits and bar connections

65 A
65 A
3
Fixed
Ref. 95334400
IEC
GB
60947-6-1
14048.11
AC-32B
AC-33iB
PC
PC
660 V 50/60 Hz
660 V 50 Hz
4000 A
4000 A
143 kA
143 kA
65 kA / 0.1s
65 kA / 0.1s
12 kV
12 kV
65 A
65 A
65 A
65 A
4
Fixed
Ref. 95333401
NOTE: Terminals RR, SS, TT and NN are each to be connected in parallel and must be bridged as shown above.
IEC
GB
Bridging bars are not included with the product and must be supplied by others.
60947-6-1
14048.11
AC-32B
AC-33iB
PC
PC
660 V 50/60 Hz
660 V 50 Hz
4000 A
4000 A
143 kA
143 kA
65 kA / 0.1s
65 kA / 0.1s
12 kV
12 kV
65 A
65 A

5.5. Busbar connection recommandations

65 A
65 A
3
Draw out
Rating
Cross section per bar
Ref. 95334401
4000 A
100mm x 10mm
IEC
GB
60947-6-1
14048.11
5000 A
100mm x 10mm
AC-32B
AC-33iB
PC
PC
660 V 50/60 Hz
660 V 50 Hz
6300 A
100mm x 10mm
4000 A
4000 A
143 kA
143 kA
65 kA / 0.1s
65 kA / 0.1s
12 kV
12 kV
65 A
65 A
65 A
65 A
4
Draw out
ATyS d H - 544077D - SOCOMEC
4000 A
Recommended tightening torque:
4000A: M12 / 45 Nm
5000A: M12 / 45 Nm
6300A: M12 / 45 Nm
4000 A
Quantity of bars per phase
4000 A
4
5
6
Maximum tightening torque:
4000A: M12 / 45 Nm
5000A: M12 / 45 Nm
6300A: M12 / 45 Nm
Type of screw
Recommended tightening torque (N.m)
M12
M12
M12
45Nm
45Nm
45Nm
EN
15