4.3.4 Language selection

English is the language automatically selected, but it can be changed into: Italian, French, German, Spanish.
To modify the language, operate as follows:
1. Press the PROGRAM key, select the MAINTENANCE item and press ENTER
2. Press ENTER in the screen A0, and UP or DOWN to modify the language
3. Press ENTER to confirm the new language.

5 ALARMS

The alarms managed by the program safeguard soundness of the connected devices and provide signals in
case the control parameters have exceeded the normal values or the board is faulty. The alarms originate
from alarm digital inputs, probes or board. Their effect ranges from the simple block signalling of one or more
devices to the air-conditioning unit stop. Many alarms are subject to programmable delay times.
When an alarm state is identified, the following signals occur:
the red LED under button ALARM turns on
abbreviation AL starts blinking on the Menu screen
Pushing button Alarm, the buzzer switches off and the alarm screen is displayed. If more alarms are active,
the screen of the first alarm is displayed; the other alarms can be displayed by using the arrow buttons. If
other buttons are pressed, the alarm screens are left but they keep stored and are displayed again whenever
the Alarm button is pressed.
To rearm the alarms and delete the message manually, simply move the cursor on the alarm screens and
push button Alarm again; if the alarm causes have disappeared (digital inputs rearmed, temperature within
the normal values, etc...), the screens disappear, the red led switches off and message "NO ALARM
ACTIVE" is displayed. If the cause of one or more alarms is still active, the disabled alarms only disappear,
whereas the other alarms keep displayed and the buzzer and the red led switch on again.
Alarms are divided into two categories: manually-rearmed alarms or automatically-rearmed alarms.
The manually-rearmed alarms require alarm screen deleting (as described above) to restart the devices or
the air-conditioning unit. The automatically-rearmed alarms unlock the device or restart the air-conditioning
unit after the cause has disappeared, but the alarm screen keeps stored in the memory.

5.1 Table of alarms

CODE
A01
Compressor 1 general alarm
A02
Compressor 2 general alarm
A03
Compressor 1 low pressure
A04
Compressor 2 low pressure
A05
No air flow
A06
Outlet fan thermal
A07
Heater 1 thermal
A08
Heater 2 thermal
A09
Fire / Smoke detection
A10
Dirty filters
A11
High ambient temperature
A12
Low ambient temperature
A13
High ambient humidity
A14
Low ambient humidity
A15
Compressor 1 working hours threshold reached
A16
Compressor 2 working hours threshold reached
A17
Outlet fan working hours threshold reached
A18
Ambient temperature probe faulty or disconnected
Recovery
water
A19
disconnected
A20
External air temperature probe faulty or disconnected
A21
Outlet air temperature probe faulty or disconnected
A22
Ambient humidity probe faulty or disconnected
A23
Condenser 1 pressure probe faulty or disconnected
A24
Condenser 2 pressure probe faulty or disconnected
A25
Condenser 1 temperature probe faulty or disconnected
A26
Condenser 2 temperature probe faulty or disconnected
A27
High humidifier current
INNOV@-pCO1-IOM-0907-E
DESCRIPTION
temperature
probe
faulty
DELAY
UNIT OFF
-
-
see T2
see T2
see T4
-
-
-
-
-
see T2
see T2
see T2
see T2
-
-
-
60 sec (fixed)
or
60 sec (fixed)
60 sec (fixed)
60 sec (fixed)
60 sec (fixed)
60 sec (fixed)
60 sec (fixed)
60 sec (fixed)
60 sec (fixed)
-
DISABLED
-
Compressor 1
-
Compressor 2
-
Compressor 1
-
Compressor 2
yes
All
yes
All
-
Heater 1
-
Heater 2
yes
All
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Humidifier
23