4.5 Other Tests

For Australian requirements, in the THDi test, Zref should be added between the inverter and
mains.
RA, XA for the line conductor
RN, XN for the neutral conductor
Zref:
RA = 0, 24, XA = j0,15 at 50Hz
RN = 0, 16, XN = j0,10 at 50Hz

4.6 Quick Checklist To Avoid Dangerous Conditions

1. The inverter must not be installed near flammable or explosive materials or near equipment
with strong electromagnetic fields. Please refer to page 6.
2. Remember that this inverter is heavy! Please be careful when lifting from the package. Please
refer to page 07
3. Make sure that the battery breaker is off and that the nominal battery voltage meets ET specifi-
cations before connecting the battery to the inverter; make sure that the inverter is totally
isolated from both PV and AC power. Please refer to page 9.
4. Make sure that the inverter is totally isolated from all DC or AC power before connecting the AC
cable. Please refer to page 11.
5. Make sure the AC cable is totally isolated from AC power before connecting the Smart Meter and
CT. Please refer to page 14.
33
Appendix protection category definition
Overvoltage category definition
Applies to equipment connected to circuits where measures have been
Category I
taken to reduce transient overvoltages to a low level.
Applies to equipment which is not permanently connected to the
Category II
installation. Examples are appliances, portable tools, and other plug-con-
nected equipment.
Applies to downstream fixed equipment and includes the main distribu-
Category III
tion board. Examples are switchgear and other equipment in an industrial
installation.
Applies to equipment permanently connected at the origin of an installa-
tion (i.e. upstream of the main distribution board). Examples are electricity
Category IV
meters, primary overcurrent protection equipment and other equipment
connected directly to outdoor open lines.
Moisture location category definition
Moisture Parameters
3K3
Temperature Range
0~+40℃
Moisture Parameters
5%~85%
Environment category definition
Environment Condition
Ambient Temperature
Outdoor
-20~50℃
Indoor Unconditioned
-20~50℃
Indoor conditioned
0~40℃
Level
4K3
4K4H
-33~+40℃
~20~+55℃
15%~100%
4%~100%
Relative Humidity
Applied to
4%~100%
PD3
5%~95%
PD3
5%~85%
PD2
34