Emerson Rosemount 3051HT Quick Start Manual page 15

Hygienic pressure transmitter with foundation fieldbus protocol
Hide thumbs Also See for Rosemount 3051HT:

Advertisement

June 2020
4. If the L_TYPE selected is Indirect or Indirect Square Root, set
OUT_SCALE to change engineering units.
5. To change damping, select Change Damping
Note
Guided setup will automatically go through each step in the proper
order.
6. Enter the desired damping value in seconds.
The permitted range of values is 0.4 to 60 seconds.
7. To configure the LCD display (if installed).
8. Select Local Display Setup.
9. Check the box next to each parameter to be displayed to a maximum
of four parameters.
The LCD display will continuously scroll through the selected
parameters.
10. To review the transmitter configuration, navigate using the manual
setup navigation sequences for "AI Block Unit Setup", "Change
Damping", and "Set up LCD Display".
11. Change any values as necessary.
12. Return to the Overview screen.
13. If mode is "Not in Service", click Change, and then select Return All
to Service.
Note
If hardware or software write protection is not needed,
be skipped.
14. Set switches and software write lock.
Quick Start Guide
a) Select OUT_SCALE UNITS from the menu.
b) Set the OUT_SCALE low value.
This may be elevated or suppressed for level applications.
c) Set the OUT_SCALE high value.
This may be elevated or suppressed for level applications.
d) If the L_TYPE selected is Indirect, guided setup automatically
places the AI block into AUTO mode to return the device to
service.
a) Check switches (see
Figure
2-4).
Quick Start Guide
Step 14
can
15