Omron SC20G2 Operation Manual page 81

Snmp/web card
Hide thumbs Also See for SC20G2:
Table of Contents

Advertisement

 The example of a time chart
Setting conditions of Master UPS
Operation
AC fail delay time (Min)
1st warning (Sec)
Warning period (Sec)
Waiting time to a UPS stop
AC failure occurring time
The setting conditions of a Slave UPS
Waiting time to a UPS stop (Sec)
The setting conditions of a client computer
AC fail delay time
Master UPS ON
Master UPS OFF
The input power
failure occurs in
the master UPS
Slave UPS ON
Slave UPS OFF
Client computer
ON
Client computer OFF
(Sec) :180(
22 : 20 : 00
22 : 30 : 00
AC fail delay time
is ends.
Shutdown command
sending
Shutdown command
reception
Shutdown command
reception
79
:client shutdown / UPS stop
:10(
)
Initial value
:30(
)
Initial value
:30(
)
Initial value
)
Initial value
:22:20:00
:300
:30 sec
22 : 33 : 00
Master UPS stop
Slave UPS stop
22 : 30 : 30
Client
The end of
computer
delay time
Power
Start OS stop
OFF
22 : 35 : 00