WIRING INSTRUCTIONS

■ TIGHTENING TORQUE
Separable screw terminal wiring screw: 0.5 N·m
Separable screw terminal fixing screw: 0.5 N·m
■ SOLDERLESS TERMINAL unit: mm (inch)
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable. Solder-
less terminals with insulation sleeve do not fit.
Applicable wire size: 0.25 to 0.75 mm
Recommended manufacturer: Japan Solderless Terminal
MFG. Co., Ltd., Nichifu Co., Ltd.
3 (.12) max.
12 (.47) max.
■ HOW TO REMOVE SEPARABLE SCREW TERMINAL
The terminal block is separable in two pieces. Evenly loos-
en two screws on top and bottom of the terminal block to
separate.
2
3.2 (.13) dia.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
PC CONFIGURATOR
The following parameter items can be set with using PC
Configurator Software (model: R30CFG).
Refer to the users manual for the R30CFG for detailed op-
eration of the software program.
■ CHANNEL INDIVIDUAL SETTING
PARAMETER
SETTING RANGE
Unused setting
CH enabled
CH disabled
Sensor type
CLSE-60
CLSE-40
CLSE-20
CLSE-10
CLSE-05
CLSE-R5
Fine zero adjustment
-320.00 – +320.00
(%)
Fine gain adjustment
-3.2000 – +3.2000
Scaled range Zero
0 – 64 000
Scaled range Span
0 – 64 000
Low-end cutout
0.5 – 50.0 (%)
■ CHANNEL BATCH SETTING
PARAMETER
SETTING RANGE
Conversion rate
80 ms
40 ms
20 ms
10 ms
Delay at power ON
0.0 – 60.0 sec.
Simulate input
Normal input
Simulated data
R30CT4E
DEFAULT
SETTING
CH enabled
CLSE-60
0.00 (%)
1.0000
0
0
1.0 (%)
DEFAULT
SETTING
80 ms
5.0 sec.
Normal input
EM-9018 Rev.2 P. 5 / 5