Parameter assignment

7.8 P010 Language

7.8
P010 Language
Values
If a language is selected, parameter titles for the parameters P000 to P010 are displayed.
7.9

P050 to P055 Volume

Note
Factory settings are indicated by an asterisk (*) in the parameter tables, unless explicitly
described.
Set SITRANS Probe LR to calculate readings based on reservoir volume instead of level.
1. Operation must be set to Level (P001 = 1).
2. Select a vessel shape matching the monitored vessel (P050).
3. If required, add dimensions A or L (as shown in the chart on page 45), using P052 and
P053, or, if vessel shape 9 is selected, add level and volume breakpoints in P054 and
P055.
4. Enter the value for the maximum vessel volume in P051.
5. Return to RUN mode: readings are now displayed in volumetric units. To select
PERCENT, press
Volume.
7.10

P050 Vessel shape

Defines the vessel shape (see chart on next page) and allows SITRANS Probe LR to
calculate volume instead of level. The default setting for P050 is 0 (volume calculation not
required).