Table 16. Multimode Optical Fiber Cable Specifications - IBM 8265 Site Preparation Manual

Nways atm switch
Hide thumbs Also See for 8265:
Table of Contents

Advertisement

Optical Fiber Cable Specifications
Recommended Optical Fiber Specifications for Commercial Building Wiring
The IBM Cabling System currently recommends 100/140-micron optical fiber for
extending token-ring transmission distances between wiring closets. But IBM now
recommends the 62.5/125-micron optical fiber for most establishment cabling
applications. The 100/140-micron optical fiber will continue to be supported for token-
ring networks and fiber distributed data interface (FDDI) networks.
The 62.5/125-micron fiber specification is patterned after the fiber specification in the
emerging Commercial Building Wiring Standard (developed by the TIA 41.8.1, and
under study by the ISO SC25/WG2 working groups) which will meet most of the intra-
building and campus link requirements. This specification is expected to become the
accepted multimode standard for government and commercial buildings and meet the
ATM and FDDI application requirements. The FDDI standard also provides the
information for attaching FDDI cable using 50/125-, 100/140-, or 85/125-micron
multimode optical fibers. IBM recommends 62.5/125-micron multimode optical fiber.
IBM also supports 50/125- (preferred in Japan and other countries), 85/125-, and
100/140-micron multimode optical fibers, as defined in the ISO 9314/ANSI X3T9.5
standard for both the token-ring networks and FDDI applications.
Each cable specification parameter must be met over the full range of operating
temperatures. A suggested temperature range of 0°C - 52°C (32°F - 125.6°F) is an
appropriate choice for many installations. Maximum summer and minimum winter
temperatures may differ from this range, particularly in installations where fiber cable
will be installed in uninsulated and unheated areas (typically building attics).
Customers should select a grade of fiber that will perform to specification in those
instances where the temperature may exceed the suggested range.
Multimode Optical Fiber Cable

Table 16. Multimode Optical Fiber Cable Specifications

Description
Core diameter
Cladding diameter
Numerical aperture
Core/cladding offset
Core non-circularity
Cladding non-circularity
Maximum Attenuation at wavelength
850 nanometers
1300 nanometers
Minimum Bandwidth at wavelength
850 nanometers
1300 nanometers (wiring closet to office)
1300 nanometers (channel extension application)
62.5/125
62.5 +/-3 µm
127 + 0/-4 µm
0.275 + /-0.015
3 µm (maximum)
6% (maximum)
2% (maximum)
3.75 dB/km
2.0 dB/km
160 MHz
500 MHz
500 MHz
Chapter 4. Planning for Fiber Connections
50/125
50 + /-3 µm
127 + 0/-4 µm
0.2 + /-0.015
3 µm (maximum)
6% (maximum)
2% (maximum)
3.5 dB/km
1.5 dB/km
500 MHz
500 MHz
800 MHz
25

Advertisement