Download Print this page

Wayne ISP40 Operating Instructions And Parts Manual page 2

Ac/dc sump pump system

Advertisement

Operating Instructions And Parts Manual
5. Connect rigid pipe to rubber boot on
Pump Installation
check valve. Tighten hose clamps.
Installation may
NOTICE
WARNING
!
take several hours.
Do not disable an existing sump pump
assembling and after installation.
until you have established an
Failure to do so could cause piping or
appropriate way to evacuate sump pit.
check valve to break, pump to fail, etc.,
1. Install pump in a sump pit with
which could result in property damage
and/or personal injury.
minimum size as shown in Figure 2.
Construct sump pit of tile, concrete,
6. Protect electrical cord from sharp
steel or plastic. If the sump pit
objects, hot surfaces, oil and
already exists, disconnect power to
chemicals. Avoid kinking the cord.
Replace a damaged cord immediately.
existing pump and make certain pit
7. A sump pit cover must be installed to
is the correct size.
prevent debris from clogging or
2. The sump pump should be located
damaging the pump.
on a solid, level foundation. Do not
place pump directly on clay, earth,
8. Fill sump with at least 6 inches of
gravel or a sandy surface. These
water.
surfaces contain small stones, gravel,
Multiple pump
sand, etc. that may clog or damage
the pump and cause pump failure.
systems
Remove any silt or debris from the
When installing more than one pump
sump pit and surrounding area.
in a sump it will be necessary to decide
Flood risk. If
WARNING
if the AC/ DC Sump Pump will be
!
flexible discharge
installed as a primary or as a back up
hose is temporarily used, make sure
pump is secured in sump pit to prevent
sump pump. The manufacturer
movement. Failure to secure pump
recommends the AC/ DC Sump Pump
could result in flooding and property
be installed as a primary pump. A
damage.
conventional AC powered electrical
back up pump can be installed
alongside as shown in Figure 3. You
will need to raise the electrical back up
pump by placing it on a brick, or by
adjusting the float so that the
electrical pump turns on above the
15"
level of the AC/ DC Sump Pump.
Min.
10" Dia.
Figure 2
Min.
Flexible discharge
NOTICE
hose is intended
for temporary use only. Rigid PVC or
metal pipe is required for a permanent
installation.
3. Thread check valve (not included)
into pump body. Avoid stripping or
cross threading. Do not use pipe
joint sealant.
4. The pump has a 1-1/2" NPT discharge.
If the existing piping is smaller, use an
adapter. Smaller diameter piping will
reduce the pump flow rate and
decrease its performance. Do not
reduce below 1 1/4".
* Assumes the sump pump is lifting water 10'
www.waynepumps.com
If the AC/ DC Sump Pump is to be used
as a backup for an electrical primary
pump it is important to maintain a
Support pump and
piping when
minimum water level of 6 inches in the
sump when measured from the bottom
of the AC/ DC Sump Pump. The water
is needed to allow the AC/ DC Sump
Pump to go through its 24-hour testing
cycle. You will need to adjust the off
level of the Electrical Primary Pump to
turn off at the minimum water level of
6 inches as shown in Figure 4.
22"
18" Min.
The on level of the Electrical Primary
Pump must turn on before the 11 inch
on point of the AC/ DC Sump Pump.
Do not raise the AC/ DC Sump Pump
above the level of the Electrical
Primary Pump.
If it is necessary to have the primary and
back up pumps discharge into a common
line, check valves will be required on
both pumps to eliminate back
reticulating flow into the inactive pump.
Battery Information
The system is designed to operate
most efficiently with sealed lead acid
(SLA) batteries at 24 volts. Two 12-volt
40-amp hour SLA batteries provide
22"
enough energy to pump more than
10,000 gallons of water from a
basement. Deep cycle marine batteries
Brick
can also be used.
Sealed lead acid batteries cost slightly
more, but they can last longer. Wayne
18" Min.
Figure 3
offers a 40 amp hour battery, 66900-
CHART 1 - STANDBY POWER PUMPING CAPACITY
Amp Hours Per Battery
Total Gallons Pumped*
40.0
11,000
80.0
22,000
120.0
33,000
2
Operating Instructions and Parts Manual
Model ISP40
Troubleshooting Chart
Problem
AC Power Indicator
(red light) is not on
Alarm sounds - yellow
light is on
Alarm sounds - yellow
light is on and red
light is off
Green Light is off
Pump will not stop
Primary
Off Point
6"
Pump will not start
Minimum
Water Level
Figure 4
Pump starts/stops too
often
Pump operates but
delivers little or no
water
"Click" inside PS/BC.
An overload is
indicated when you
hear a distinct "click"
from the DC circuit
breaker internal to the
PS/BC. A 3-5 minute
cooling off period
occurs before the PS/BC
resets itself. If the
overload condition still
exists, the cycle will
repeat. Regardless of
what is causing the
circuit breaker to cycle,
unattended or routine
operation in this
manner could result in
serious damage to the
PS/BC and the battery.
Possible Cause(s)
Corrective Action
1. Power outage
1. None
2. Blown AC breaker
2. Push AC breaker to reset. If breaker trips again, do not reset.
Have unit checked by qualified electrician
3. GFCI tripped
3. Reset GFCI
4. Low AC voltage
4. Have outlet checked by electrician
1. Pump fuse may be blown
1. Replace pump fuse. Use Bussmann AGC10 or Littlefuse 312010
2. Pump impeller may be
2. Remove impeller. Check for damage to bore or bearing
damaged
Low battery
Apply AC power or replace batteries
1. Battery polarity is incorrect
1. Recheck battery polarity
2. Battery voltage too low
2. Replace batteries
1. Lower float stuck
1. Remove filter and clean. Remove debris from float switch area
2. Pump too low in sump
2. Place a brick under the pump
1. Pump power cord
1. Check for proper installation of power cord into the PS/BC
2. Upper float switch stuck
2. Remove filter and clean. Remove debris from float switch area
3. Impeller rotor jam
3. Remove filter and clean. Remove debris from float switch area
1. Backflow from discharge
1. Install or replace check valve
pipe
2. Pump too low in sump
2. Place a brick under the pump
3. Clogged pump filter
3. Remove filter and clean
1. Blocked discharge pipe
1. Check for restrictions in discharge line, flood is immanent. Shut
off AC power before entering flooded area
2. Partially clogged pump
2. Remove impeller, check for debris in inlet
filter
3. Broken thrust bearing
3. Remove and inspect thrust bearing
1. Discharged battery
1. If the battery is in otherwise good condition, it is normal for
the circuit breaker to cycle ON and OFF several times before
the battery recovers enough to allow a normal charge rate. If
this happens on a regular basis, however, the batteries may be
too large for the PS/BC and it could be damaged. Replace
batteries
2. Shorted cell battery
2. A battery in this condition may cause the breaker to cycle
continuously. The battery will not accept a charge. Replace
both batteries
7
Model ISP40
www.waynepumps.com

Advertisement

loading