Chart 1 -
Setup Menu
Prompts and
Descriptions.
Parameters
Setup
LOC
In
r S P
DEC
C-F
rL
rH
Otl
ot2
ALt
LAt
SIL
rtd
Chart 2-
Input Ranges.
26
WATLOW Series 980/985 User's Manual
Latching: Selects whether the
is an alarm. Latching alarms must be cleared before the alarm output will reset.
Non-latching automatically resets the alarm output when the condition clears.
The range is LAt or nLA, default is nLA. This only appears if the Ot2 = AL.
Silencing: Selects alarms silencing (alarm inhibit). Appears only when
ALt = dE. If LAt, press the Auto/Man key to reset the alarm output. If nLA, alarm
automatically resets 5 seconds after power is applied.
RTD: Selects the RTD calibration curve. JIS = 0.003916 / PC
DIN =0.003850 / °C.
Use this page as a master copy for configuring your Series 980/elects the low
limit of the Operating range See the model number and specification informa-
Value
Input
Type
Sensor Range Low
J
32°F/0°C
32°F/0°C
K
-328°F/-200°C
n
32°F/0°C
Pt2
32°F/O°C
rtd
(1°)
-328°F/-200°C
rt.d (0.1') 1
-99.9°F/-99.9°C
0-5 (VDC) 1
-5.00/-50.0/-500
420 (mA)
output
is latching or non-latching when Output 2
Range
0-3
(appears as H), t, n,
J, K
Pt2, rtd, rt.d, 0-5,4-20
Dependent on model number.
OFF, O-5,420
0, 0.0,
or
0.00
Dependent on input type.
C or F
Will not appear if In = 0-5 or 420.
rLtorH
rH to rL
Ht or CL
or no
Ht. CL, AL
Pr or dE
Dependent on Ot2 = AL.
LAt or nLA
Dependent on Ot2 = AL.
OFF or On
Appears if Ot2=AL&ALt=dE.
JIS or din
Appears if In = rtd or rt.d.
Sensor Range High
999*F/750°C (3 digit)
1 382°F/750°C (4 digit)
2282°F/1250°C
2282°F/1 250°C
2543°F/l395°C
111 2°F/600°C
392.0°F/200.0°C
I
35.00/350.0/3500
35.00/350.0/3500
Factory Default
0
J
OFF
0
F
selection
Input
dependent.
Input selection dependent.
Ht
AL
Pr
nLA
OFF
JIS
I
I
Setup,
Chapter 4