Primary Output (Heating or Cooling)
Solid state relay, 0.5A @ 24VAC minimum, 253VAC maximum, opto-
l
isolated, zero cross switching.
Electromechanical relay, Form C, 6A @ 115/230VAC, 6A @ 28VDC,
l
1/8 hp. @ 115VAC 125VA @ 115VAC. Warranted to 100,000 cycles.
Open collector, switched DC signal provides a minimum turn ON voltage of
l
3VDC into a minimum 500 ohm load, maximum ON voltage not greater than
32VDC into an infinite load.
4-20mA reverse acting into a 600 ohm maximum load.
l
Secondary Output (Heat, Cool or Alarm)
Solid state relay, 0.5A @ 24VAC minimum, 253VAC maximum, opto-
l
isolated, zero cross switching.
Electromechanical relay, Form A, 6A @ 115/230VAC, 6A @ 28VDC,
.
1/8 hp. @ 115VAC, 125VA @ 115VAC. Warranted to 100,000 cycles.
Open collector, switched DC signal provides a minimum turn ON voltage of
l
3VDC into a minimum 500 ohm load; maximum ON voltage not greater than
32VDC into an infinite load.
Accuracy
Calibration Accuracy: ± 0.1% of span, ± 1 LSD,
l
77°F ± 5°F (25°C ±3°C) ambient & rated line voltage ± 10%.
Accuracy Span: 1000°F or 540°C minimum.
l
Temperature Stability: 0.1 °F/°F (0.1 °C/°C) change in ambient.
l
Voltage Stability: ± 0.01% of span per percent of rated line voltage.
l
Agency Approvals
UL recognized, File #E43684, UL873
l
CSA file #LR30586
l
Terminals
#6 compression type screw terminals
l
Power
.
115/230VAC +1 0%, -15%, 50/60Hz, ± 5%
.
10VA maximum
Data retention upon power failure via nonvolatile memory
l
Operating Environment
32 to 1 30°F/0 to 55°C.
l
0 to 9O% RH, non-condensing.
l
Dimensions
(985 orientation) For 980 units, switch height and width measurements.
H e i g h t :
l
W i d t h :
l
Overall depth:
l
Behind panel depth:
l
W e i g h t :
l
Appendix
3.8 in.
(96.5 mm)
1.9 in.
(48.0 mm)
6.3 in.
(160.5 mm)
6.0 in.
(152.5 mm)
0.9 lb.
(0.4 kg)