DO_AUX1
(only if the relay board is installed (not supplied as standard)) to bring a
phase (230Vac) to a second heating pump (additional pump) or a zone valve.
The factory setting for this parameter is 0 and can be set within the 0 - 2
range with the following meaning:
Pin 1 and 2 of X21
Not present
additional pump
management
zone valve
management
additional pump
management
EXHAUST PROBE RESET
This parameter allows operating hours meter to be reset in certain conditions
(see "4.20 Lights and faults" for more information, E091 faults).
hours meter after the primary heat exchanger has been cleaned.
to 0.
CH
HYST ON HIGH TEMP
For high temperature systems, this parameter allows you to set the
hysteresis value used by the adjustment board for calculating the ignition
delivery temperature of the burner:
TEMP.
The factory setting for this parameter is 5°C, it can be changed within the
2 - 10°C range.
HYST OFF HIGH TEMP
For high temperature systems, this parameter allows you to set the hysteresis
value used by the adjustment board for calculating the switching off delivery
temperature of the burner:
TEMP.
The factory setting for this parameter is 5°C, it can be changed within the
2 - 10°C range.
HYST ON LOW TEMP
For low temperature systems, this parameter allows you to set the hysteresis
value used by the adjustment board for calculating the ignition delivery
temperature of the burner:
The factory setting for this parameter is 3°C, it can be changed within the
2 - 10°C range.
HYST OFF LOW TEMP
For low temperature systems, this parameter allows you to set the hysteresis
value used by the adjustment board for calculating the switching off delivery
temperature of the burner:
TEMP.
The factory setting for this parameter is 3°C, it can be changed within the
2 - 10°C range.
PUMP CONTROL TYPE
Objective variable speed pump
Proportional variable speed pump
For details see paragraph "3.11 Variable speed circulator".
CH POST CIRC
NOT AVAILABLE ON THIS MODEL
LOW NOISE
NOT AVAILABLE ON THIS MODEL
SCREED HEATING
This parameter allows you to activate the screed heating function (see
paragraph "4.15 Screed heating function" for more details).
The factory setting is 0, with the boiler set to OFF, set to 1 to activate the
screed heating function on the low temperature heating zones.
The parameter automatically returns to 0 once the screed heating function is
Jumpered
ANTI CYCLE FUNCTION
zone valve
management
regarding the delay time introduced for re-igniting the burner in the face of an
zone valve
off due to the heating temperature being reached. The factory setting for this
management
parameter is 3 minutes and can be set to a value between 0 min and 20 min.
additional pump
management
RESET CH TIMERS
speed of the fan is limited to 75% of the maximum heating output that has
been set.
The factory setting for this parameter is 0, set 1 to reset the timings.
MAIN ZONE ACTUATION TYPE
and an additional pump on the main heating system (the use of the BE16
accessory board is required, not supplied as standard).
The factory setting for this parameter is 0, set to 1 for the connection of a
BE16 board.
Note: this parameter cannot be changed when an OT+ chronothermostat is
connected.
MAIN ZONE ADDR
the address of the BE16 board.
The factory setting for this parameter is 3 and can be set within the 1 - 6
range.
Note: see the instruction sheet of the BE16 accessory board for more
information about the use of this parameter.
MAIN ZONE HYDRAULIC CONF
The factory setting for this parameter is 0 and allows a direct zone to be
managed, set the parameter to 1 for the management of a mixed zone.
Note: see the instruction sheet of the BE16 accessory board for more
information about the use of this parameter.
MAIN ZONE TYPE
This parameter allows you to specify the type of zone to be heated, it is
possible to choose from the following options:
MAX CH SET
This parameter allows you to specify the maximum heating setpoint that
can be set:
- range 20°C - 80.5°C, default 80.5°C for high temperature systems
- range 20°C - 45°C, default 45°C for low temperature systems.
MIN CH SET
This parameter allows you to specify the minimum heating setpoint that can
be set:
- range 20°C - 80.5°C, default 40°C for high temperature systems
- range 20°C - 45°C, default 20°C for low temperature systems.
OTR
This parameter allows you to activate the thermoregulation when the system
has an outdoor temperature probe connected.
parameter on 1 and an outdoor temperature probe connected, the boiler
operates in thermoregulation.
With an outdoor temperature probe disconnected the boiler always operates
See paragraph "4.5 Setting the thermoregulation" for more details about this
function.