2. Product Data
2-1-3. Correction by relative humidity
[EAHV]
■Heating capacity correction diagram (relative humidity correction diagram)
The heating capacity changes depending on the relative humidity.
When the relative humidity is other than RH=85%, correct the capacity based on the following graph.
[Example] When the outdoor air temperature = 0°C and relative humidity RH=50%
Heating capacity in performance diagram × 0.926 <Correction value> = Heating capacity after correction
1.00
0.98
0.96
0.94
0.92
0.90
0.88
0.86
0.84
0.82
0.80
■Heating capacity reduction factor by frosting (reference)
Outdoor air temperature (DB)
Heating capacity reduction factor
* In the actual setup status, there are factors (weather, outside wind, relative humidity, etc.) other than outdoor air temperature,
so consider the above factors as references.
MEES19K040
Relative humidity correction diagram <50/60Hz>
-10
-5
Outdoor air temperature (°CDB)
-7°C
0.87
0
5
10
-5°C
-3°C
0.87
0.86
0.84
85%
80%
70%
60%
50%
40%
30%
15
0°C
3°C
5°C
0.87
0.98
7°C
1.00
42