3. Installation

3-1. Selecting the Installation Site

3. Installation
3-1-1. Installation Conditions
Select the installation site in consultation with the client.
Select a site to install the unit that meets the following conditions:
The unit will not be subject to heat from other heat sources.
The noise from the unit will not be a problem.
The unit will not be exposed to strong winds.
Water from the unit can be drained properly.
Enough space for installation and service as shown in 3-1. Selecting the Installation Site.
There is a possibility of injuring with the fin of the heat exchanger, so abide by following contents.
1) Limit the access of the general public to the location where they can touch the product.
2) Take a measure so the general public cannot easily access the location where they can touch the product.
3) When installing in a location where the general public can touch the product, install the optional fin guard.
Option Parts: DT-150FG
When two units are joined
Unit
Unit
DT-150FG x2
1. Protection against winds
Pay attention to the wind direction and installation location to ensure that the air heat exchanger is not directly exposed
to strong winds.
If unable to avoid strong winds, install wind breaking hoods or walls, etc.
2. Cold Climate Installation
Observe the following when installing the units in areas where snow or strong winds prevail.
Avoid direct exposure to rain, winds, and snow.
If the unit is installed in the direct line of rain, winds, or snow, install snow hoods. Use a snow net or snow fence as
necessary to protect the unit.
Install the unit on a base approximately twice as high as the expected snowfall.
If the unit of heating mode is continuously operated for a long time with the outdoor temperature below the freezing point,
install a heater at the drain pan of the unit to prevent freezing of drain.
3. Weight
Standard piping
EAHV
Inside header piping
Standard piping
EACV
Inside header piping
* Weight of the optional parts: DT-01HK (29 kg), DT-02HK (42 kg), DT-150FG (13 kg)
MEES19K040
or
Unit
Unit
DT-150FG x1
Net weight (kg)
1310
1326
1240
1256
Operating weight (kg)
1337
1394
1267
1324
52