Sound Pressure Levels - Mitsubishi Electric E Series Data Book

Air cooled chilling unit
Hide thumbs Also See for E Series:
Table of Contents

Advertisement

2. Product Data

2-2. Sound pressure levels

Measurement condition
EAHV-P1500, 1800YB
EACV-P1500, 1800YB
Sound pressure level
The following values are the planned value.
Sound pressure level dB <A> (anechoic room level)
Measurement location
Service surface: A
Counter service surface: B
Right surface: C
Left surface: D
* The above values are obtained by converting the values measured in location with less echo sound to the anechoic room level.
The values could be larger than those values if the operating conditions are different or the measuring location is affected by echo sound.
(It could be roughly 4 dB to 6 dB higher though it depends on the installation conditions.)
Regarding the installation, consider the effect of echo sound, implement soundproof treatment as necessary.
MEES19K040
EAHV-P1500YB
EAHV-P1800YB
EACV-P1500YB
EACV-P1800YB
66
66
68
70
Unit operating condition: Full load operation
(Around the unit must be completely free)
68
67
71
70
47