Advertisement

5. Wiring Design
Priority order of the water-temperature-setting-input-signal sources
Water temperature can be controlled by using the signals from the four types of input sources listed below.
The setting for the item with higher priority will override the settings for the items with lower priorities.
The water temperature will be controlled according to the temperature setting in the "Target water temperature"
column that corresponds to a specific combination of the settings for the four items.
No-voltage contact input K93-K94 ON: Heating (EAHV-P****YB, EAHV-P****YB-H)
Priority 1
No-voltage contact
Analog input or
input K40-K41
(SW 2-9: ON)
Anti-freeze
ON
SW2-7: ON
OFF
SW2-7: OFF
*1: This mode is disabled in EAHV-P****YB-H.
*2: EAHV-P****YB can also set Cooling.
*3: AE-200 and BMS cannot both be simultaneously connected. Only connect one or the other.
No-voltage contact input K93-K94 OFF: Cooling (EAHV-P****YB, EACV-P****YB)
* When the operation mode is Cooling, K40-K41 (Anti-freeze) and K40-K42 (Mode change) are disabled.
Priority 1
Analog input
No remote controller
SW2-7: ON
When no RC is used
SW2-7: OFF
*1: This mode is disabled in EACV-P****YB.
*2: EAHV-P****YB can also set Heating or Heating ECO.
*3: AE-200 and BMS cannot both be simultaneously connected. Only connect one or the other.
Priority order of the operation signal sources
Unit operation (Run/Stop)
Operation mode
Fan mode
(The contact ON has priority.)
*1: When the Anti-freeze contact is ON during heating operation, the setting change is ineffective.
*2: Changing by contact is effective during heating operation.
MEES19K040
Priority 2
Priority 3
No-voltage contact
input K40-K42
BMS
Mode change
No remote controller
Ineffective
Ineffective
Ineffective
ON
(Heating ECO)
When no RC is used
OFF
(Heating)
Priority 2
Remote controller PAR-W31MAA
Input from centralized controller AE-200 or BMS (*3)
Manual setting
-
Ineffective
-
Anti freeze (*1)
-
Heating ECO (*1)
-
Heating (*1)
-
Cooling
-
No-voltage contact
Cooling *1
Heating *1
Heating ECO *1*2
Anti-freeze *2
OFF
ON
Priority 4
Remote controller PAR-W31MAA
Input from centralized controller AE-200 or BMS (*3)
Manual setting
-
Ineffective
-
Ineffective
-
Ineffective
-
-
Anti-freeze
-
Heating ECO
-
Heating
-
Cooling (*1)
-
-
Schedule setting
Ineffective
-
-
-
-
-
-
When schedule has
-
been set (*2)
Remote controller
PAR-W31MAA
The last setting has priority.
The last setting has priority.
The last setting has priority.
The last setting has priority.
The last setting has priority.
The last setting has priority.
Target water temperature
Schedule setting
Ineffective
30ºC
Temperature setting for
Ineffective
the analog signal input
Ineffective
Heating ECO
-
Heating
-
30ºC
-
Heating ECO
-
Heating
-
Cooling
Target water temp is
When schedule has
controlled according to
been set (*2)
the setting on the remote
controller.
Target water temperature
Temperature setting for the
analog signal input
Cooling
30ºC
Heating ECO
Heating
Cooling
Target water temp is controlled
according to the setting on the
remote controller.
Input from centralized
controller AE-200 or BMS
Ineffective
71