3. Installation
3-2-2. Installation on foundation
Securely fix the unit with bolts to keep the unit from falling down during earthquakes.
Install the unit on a foundation made of concrete or iron.
Noise and vibrations from the unit may be transmitted through the floor and walls. Provide adequate protection against
noise and vibration.
Warning:
Be sure to install the unit on a surface strong enough to withstand its weight to keep the unit from falling down
and causing injury.
Provide adequate protection against earthquakes. Improper installation may cause the unit to fall down, result-
ing in personal injury.
When building the foundation, take the floor strength, and piping and wiring routes into consideration.
Foundation
106
(56)
MEES19K040
Bolt size
Number
M16
4
[Enlarged view]
Unit
Base frame
Damper pad
Adhesive
Drain discharge hole 3-ø50
Foundation
1032
1088
100
3280 (Anchor bolt hole pitch)
show mounting surface.
*
Foundation
Base surface
(unit bottom)
608
106
1309
56
Unit: mm
4-ø20 holes
Bolt size: M16
56