BTL5-T1_ _-M_ _ _ _-P-S103
Micropulse Linear Transducer – Profile Housing
6

Startup

6.1

Check connections

Although the connections are po-
larity reversal protected, compo-
nents can be damaged by im-
proper connections and
overvoltage. Before you apply
power, check the connections
carefully.
6.2

Turning on the system

Note that the system may execute
uncontrolled movements when first
turned on or when the transducer is
part of a closed-loop system whose
parameters have not yet been set.
Therefore make sure that no haz-
ards could result from these situa-
tions.
7

Versions (indicated on part label)

Supply voltage: 1 = DC 24 V
Type: BTL5-T110-M1000-P-S103
Type No. of magnets
1
Ordering code: BTL_ _ _ _
7.1
Available stroke lengths
and magnets
To provide for optimum fit in any
application, a wide range of stan-
dard stroke lengths and magnets
in various form factors are avail-
able. Magnets and control arms
must therefore be ordered sepa-
rately.
The following nominal stroke
lengths are available:
10
english
6.3

Check output values

After replacing or repairing a trans-
ducer, it is advisable to verify the
values for the start and end position
of the magnet in manual mode. If
values other* than those present
before the replacement or repair are
found, a correction should be made.
* Transducers are subject to modifi-
cation or manufacturing tolerances.
6.4

Check functionality

The functionality of the transducer
system and all its associated com-
ponents should be regularly
checked and recorded.
Electr. connection,
Connector variations:
S103 = 1 × 3-pin male
1 × 5-pin male
1 × 5-pin female
Profile housing
Nominal stroke (4 digits): M = Metric units [mm]
1 - 4 selectable using GSD
Stroke lengths
[mm]
2000
Other stroke lengths on request.
7.2

Included in shipment

Transducer (with mounting brack-
ets, isolation bushings and
screws, not incl. magnet)
➥ ➥ ➥ ➥ ➥ Figs. 3-1 and 3-2
and condensed guide
Increments
[mm]
... 1000
50
...
2000
100
...
4000
250
6.5

Fault conditions

When there is evidence that the
transducer system is not operating
properly, it should be taken out of
service and guarded against unau-
thorized use.
6.6

Noise elimination

Any difference in potential - cur-
rent flow - through the cable shield
should be avoided. Therefore:
– Use the isolation bushings, and
– Make sure the control cabinet
and the system in which the
BTL5 is contained are at the
same ground potential.
7.3

Software

Download the GSD file from
www.balluff.de ..... or via e-mail
to PROFIBUS@balluff.de.