Connecting
4.1
Basic safety notes
Unsuitable cables, cable glands and/or plugs
Risk of explosion in hazardous areas.
● Use only cable glands/plugs that comply with the requirements for the relevant type of
● Tighten the cable glands in accordance with the torques specified in Technical data
● Close unused cable inlets for the electrical connections.
● When replacing cable glands, only use cable glands of the same type.
● After installation, check that the cables are seated firmly.
Incorrect conduit system
Risk of explosion in hazardous areas as result of open cable inlet or incorrect conduit system.
● In the case of a conduit system, mount a spark barrier at a defined distance from the device
See also
Technical data (Page 53)
Hazardous contact voltage
Risk of electric shock in case of incorrect connection.
● For the electrical connection specifications, refer to the information in Technical data
● At the mounting location of the device observe the applicable directives and laws for
SITRANS MASS 2100 & FC300 (FCT030)
Compact Operating Instructions, 05/2020, A5E40533698-AC
WARNING
protection.
(Page 53).
WARNING
input. Observe national regulations and the requirements stated in the relevant approvals.
WARNING
(Page 53).
installation of electrical power installations with rated voltages below 1000 V.