Connecting
4.1
Basic safety notes
Unsuitable cables, cable glands and/or plugs
Risk of explosion in hazardous areas.
• Use only cable glands/plugs that comply with the requirements for the relevant type of
• Tighten the cable glands in accordance with the torques specified in Connecting the sensor
• Close unused cable inlets for the electrical connections.
• When replacing cable glands, only use cable glands of the same type.
• After installation, check that the cables are seated firmly.
Hazardous contact voltage
Risk of electric shock in case of incorrect connection.
• For the electrical connection specifications, refer to the information in Technical
• At the mounting location of the device observe the applicable directives and laws for
NOTICE
Condensation in the device
Damage to device through formation of condensation if the temperature difference between
transportation or storage and the mounting location exceeds 20 °C (36 °F).
• Before taking the device into operation, let the device adapt for several hours in the new
SITRANS FS130 & FS230
Compact Operating Instructions, 12/2023, A5E38755607-AF
WARNING
protection.
cables (internal DSL only) (Page 39).
WARNING
specifications (Page 97).
installation of electrical power installations with rated voltages below 1000 V.
environment.
4