4.2

Connecting MASS 2100/FC300

4.2.1

Cable requirements

● When installing sensor cable, use cable with at least same degree of protection as the
sensors. It is recommended to use cables supplied by Siemens:
– blue cables for installation of intrinsically safe circuits in hazardous areas
– gray cables for installation of non-intrinsically safe circuits
Further information on Siemens-supplied cables, see Technical data (Page 53).
● The wire length inside the connection compartment, from the cable gland to the terminals,
must be kept as short as possible. Wire loops in the terminal compartment must be avoided.
● To guarantee the degree of ingress protection, ensure that both ends of the cables are given
equivalent protection from ingress of moisture.
Cable requirements
Cables must be suitable for the temperature (at least 70 °C) and be flammability-rated to at
least V-2.
Note
Output cables
If long cables are used in extreme EMC environments, it is recommended to use shielded
cables.
4.2.2

Connection safety information

Tightness
Only when the cable is connected to the sensor, the IP67 protection is achieved.
Installation in hazardous areas
When making electrical connections, observe the national statutes and provisions for
hazardous areas valid for the particular country.
● Operational safety regulations
● Directive for the installation of electrical systems in hazardous areas DIN EN 60079-14
SITRANS MASS 2100 & FC300 (FCT030)
Compact Operating Instructions, 05/2020, A5E40533698-AC
WARNING
WARNING
WARNING
4.2 Connecting MASS 2100/FC300
Connecting
33