3. INSTALLATION

3.3.6 Supply air temperature duct sensor

The supply air duct sensor has to be installed after connecting the DanX unit to the duct
system. You find the coiled up (10m) sensor on the top deck of the unit.
The duct sensor is installed in the supply air duct of the swimming pool, after the heating coil
in the following way.

3.3.7 Return air humidity / temperature duct sensor

The return air temperature and humidity sensor has to be installed after connecting the DanX
unit to duct system. You find the coiled up (10m) sensor on the top deck of the unit.
The duct temperature / humidistat sensor is installed in the return air duct from the swimming
pool. Please follow the instructions, following with the duct sensor.

3.3.8 Room air humidity / temperature sensor

If you have ordered a room thermostat / humidistat sensor instead of a duct mounted on, this
will only be connected to the terminal strip of the unit with a short cable to test the function.
When installing the unit you have to replace this cable with a cable of the right length, to
connect the room temperature / humidistat sensor between the pool room and the unit.
The room temperature/humidistat sensor should be installed at a height of minimum 2,5m and
not above doors where people entering or leaving the pool hall. Secondly the sensor should
not be placed where heating, ventilation or the sun can have an influence on the measuring
result. Otherwise please follow the instructions, following with the room sensor.

3.3.9 Separate outdoor sensor

If there is ordered a separate outdoor temperature sensor, you will find the sensor separately
in the electrical panel without cabling. Install the sensor outside the building where there is no
direct sunlight. Disconnect the standard outdoor sensor which is installed inside the DanX unit
(see electrical diagram) and connect the new outdoor sensor to the two terminals.
Drill an 8 mm hole in the supply air duct at least 1.5 m from the last component of the
unit.
Place the sensor in the hole.
Fasten the sensor housing to the duct with two screws and close the sensor.