3. INSTALLATION

3.7 Installation of electrical components

If the DanX AF unit is equipped with an MVC 80 electrical panel, the component has to be
installed in the following way. The functions of the MVC 80 panel are explained in a separate
instruction manual.

3.7.1 Supply air temperature duct sensor

The supply air duct sensor has to be installed after connecting the DanX unit to the duct
system. You find the coiled up (10m) sensor on the top deck of the unit.
The duct sensor is installed in the supply air duct of the swimming pool, after the heating
coil in the following way.

3.7.2 Return air humidity / temperature duct sensor

The return air temperature and humidity sensor has to be installed after connecting the
DanX unit to duct system. You find the coiled up (10m) sensor on the top deck of the unit.
The duct temperature / humidistat sensor is installed in the return air duct from the
swimming pool. Please follow the instructions, following with the duct sensor.

3.7.3 Room air humidity / temperature sensor

If you have ordered a room thermostat / humidistat sensor instead of a duct mounted on, this
will only be connected to the terminal strip of the unit with a short cable to test the function.
When installing the unit you have to replace this cable with a cable of the right length, to
connect the room temperature / humidistat sensor between the pool room and the unit.
The room temperature/humidistat sensor should be installed at a height of minimum 2,5m
and not above doors where people entering or leaving the pool hall. Secondly the sensor
should not be placed where heating, ventilation or the sun can have an influence on the
measuring result. Otherwise please follow the instructions, following with the room sensor.
Drill an 8 mm hole in the supply air duct at least 1.5 m from the last component of the
unit.
Place the sensor in the hole.
Fasten the sensor housing to the duct with two screws and close the sensor.