5. MAINTENANCE

5.4 Fans

The following general steps should be taken to maintain the fans:
Check the fan wheel for unbalance (every 3 month).
Check the fan and motor bearings for unusual noise (every 3 month).
Check vibration dampers for damage (every 3 month)
Check the fan for dust or dirt. If necessary, clean the fan wheel, either dry or wet (every
12 month).
Check all flexible connections for damage/leakage (every 12 month).
Check if all mounting bolts are tight (every 12 month).
Check the pressure hoses from the pressure transmitter to the fan for leakage or
damage (every 3 month).

5.5 Filter

If the filters are equipped with a pressure transducer the control panel automatically gives an
alarm when the filters have to be changed. Still every 6 month the filters should be checked
for damage/leakages which will not be detected by the pressure transmitter. If no pressure
transmitter is installed the following steps should be taken every 6 month:
Check the filter for dirt and damage.
Measure the pressure loss over the filter which should not be below 150 Pa (G3/G4) or
250 Pa (F5/F7). If the pressure loss is higher the filters have to be changed.
Open the filter rail by the blue handles (1).
Take out the filters (2) and check the gasket on the filter rail for damage.
Clean the filter rail and reinstall the old/new filters.
25