Overview of Analog Units

5-1

Overview of Analog Units

5-1-1

Analog Units

5-1-2

Comparison with Earlier Models

Analog Input Units
Unit
Model
Analog points
Input range (signals)
AD conversion cycle
AD conversion data
Resolution
Unit power supply
Communications power supply cur-
rent consumption
Overall accuracy 25°C
−10 to 55°C
Allocated I/O data
Input switching (Sets number of AD
conversion points)
Input range switching
Node address setting
68
This section provides an overview of Analog Units, including details on func-
tions and setting methods for each Unit.
In addition to the functions common to the GRT1 Series (backup, restore,
online conversion, etc.), other functions specific to Analog Units (scaling,
peak/bottom hold, etc.) are available. Analog Input Units are also able to inter-
nally perform math on analog input values, which previously required ladder
programming in the host PLC. Analog data can be selected from the six val-
ues obtained from math operations and allocated as I/O in combination with
Generic Status Flags or other status information. The Setting Tool can be
used to allocate this status data, and to set functions specific to Monitor/Ana-
log Units and perform monitoring.
GRT1 Series
GRT1-AD2
2 inputs
0 to 5 V, 1 to 5 V, 0 to 10 V, –10 to 10 V, 0 to 20 mA, 4 to 20 mA
2 ms/2 points
0 to 5 V, 1 to 5 V, 0 to 10 V, 0 to 20 mA, 4 to 20 mA: 0000 to 1770 hex
–10 to 10 V: F448 to 0BB8 hex
Note Two's complement
1/6,000 (full scale)
Supplied from slice bus.
None
±
Voltage input:
0.3% FS; Current input:
±
Voltage input:
0.6% FS; Current input:
Default: Analog input values for 2
points
A Setting Tool can be used to allocate
peak, bottom, top, and valley values,
rate of change, comparator results,
etc.
Supported. (Set using DIP switch:
Select either 1 or 2 points)
Using DIP switch: Inputs 0 and 1 share
setting.
Using Setting Tool: Can be set sepa-
rately.
No setting required.
DRT2 Series
DRT2-AD04
4 inputs
By setting the number of conversion
points (1 to 4 points), the conversion
cycle can be shortened (e.g., 4 points:
4 ms max.)
Note The conversion cycle will be
slightly different when the math
operations are used.
Supplied from communications power
supply.
90 mA max.
±
0.4% FS
±
0.8% FS
Default: Analog input values for 4
points
A DeviceNet Configurator can be used
to allocate peak, bottom, top, and val-
ley values, rate of change, comparator
results, Generic Status Flags, etc.
Supported (Set using DeviceNet Con-
figurator: Select from 1 to 4 points)
• Using DIP switch: Inputs 0 and 1
share setting, Inputs 2 and 3 share
setting.
• Using DeviceNet Configurator: Inputs
0 to 3 set separately.
Set using the rotary switches or the
DeviceNet Configurator.