DT7000
Media compatibility
Pressure compatibility Check that the maximum pressure occur on the pressure
Mounting position
Shock, vibration
Water, humidity
20171206-V1

4. Mounting

4.1. General Instructions

Please respect the followings. Inappropriate or incorrect use
or mounting may cause measuring failure or damage of the
instrument.
The sensing element materials of the DT7000 are silicon
diaphragm, glass filled nylon and alumina ceramic.
Apply dry air only!
ports is always under the allowable value given on the data
label.
Measures differential or gauge pressure only with positive
pressure to port P+.
The instrument should be where in vertical position Select a
mounting position you can easily read the display reach for
mounting and connecting the instrument and that reduce the
hazard of water, dust or dump getting into the instrument.
Avoid shock or vibration during mounting and operation.
After mounting the instrument it is suggested to check the
zero on the display especially in case of < 300 Pa measuring
range.
If the displayed value is > 1 digit in case of open pressure
ports you can adjust it according Chapter 6.1. Zeroing.
The protection of the instrument is IP 65.
In a case of using DT7000 outdoor mount a shield over the
instrument to protect it against strong rain.
9