Page 1
eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3), Revision J Specification Number: 1S482000e3 Model Number: S48-2000e3...
Page 2
This document may contain confidential and/or proprietary information of Vertiv Group Corp., and its receipt or possession does not convey any right to reproduce, disclose its contents, or to manufacture or sell anything that it may describe. Reproduction, disclosure, or use without specific authorization from Vertiv Group Corp.
Solar Converter High Voltage Shutdown and Lockout Restart ......19 Installing Solar Converters ......................... 21 Troubleshooting and Repair ................22 Troubleshooting ..............................22 Replacement Procedures ........................... 24 Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
SAFETY! Informs the reader of general safety information, reminders, precautions, or policies not related to a particular source of hazard or to fire safety. (ISO, ANSI, OSHA) Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
NEVER allow a metal object, such as a tool, to contact more than one termination or battery terminal at a time, or to simultaneously contact a termination or battery terminal and a grounded object. Even a momentary short circuit can cause sparking, explosion, and injury. Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
ALERT! Installation or removal of equipment containing static sensitive components requires careful handling. Before handling any equipment containing static sensitive components, read and follow the instructions contained on the Static Warning Page. Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
If necessary to repair equipment containing static sensitive components, wear an appropriately grounded wrist strap, work on a conductive surface, use a grounded soldering iron, and use grounded test equipment. Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
Page 8
This page is intentionally blank. Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
• Output Characteristics: Refer to Figure 1 for a graph of output voltage vs. output current. Figure 1: Output Voltage vs. Output Current Output Voltage vs. Output Current at Max. Power Output Current (A) Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
Page 10
+55 °C (+131 °F). Refer to Figure 4 to view the relationship between the output power and the ambient temperature with the input voltage and output voltage within these ranges. Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
Page 11
Telcordia GR-947-CORE, the maximum voltage transient will not exceed 5% of the initial steady state voltage within 50±10 microseconds. Recovery to within 1% of the initial steady state voltage does not exceed 1 milliseconds. Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
Page 12
X and Y filter capacitors shall be ignored. • Typical Input Data: Refer to Table 1. Maximum Input Current: 12 A. Efficiency Curve: Refer to Figure 5. Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
Page 14
Degree 2 or less. Pollution Degree 2 applies where there is only non-conductive pollution that might temporarily become conductive due to occasional condensation (such as the office environment). Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
Page 15
At input voltage of 176 V with output >48 V, maximum output power is 1760 W. At input voltage of 200 V and output >48 V, maximum output power is 2000 W. Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
Page 16
The total system current is divided by the quantity of power modules installed in the system to determine the per module average load that each module should deliver. Each module Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
Page 17
The DSP also communicates with the controller in real time through the CAN bus. Table 2 lists the different commands and information exchanged between the solar converter and the controller. Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
Page 18
Millimeters: 41.0 (Height) X 84.5 (Width) X 252.5 (Depth) Inches: 1.6 (Height) X 3.3 (Width) X 9.9 (Depth) • Weight: 1.13 kg (2.49 lbs) • Indicators: Power (Green LED) Protection (Yellow LED) Alarm (Red LED) Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
Solar Converter High Voltage Shutdown and Lockout Restart Procedure Remove the solar converter, wait 30 seconds or more (until the LEDs on the solar converter extinguish), then re-insert the solar converter. Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
Page 20
Solar converter output disabled for any reason, including overvoltage shutdown and internal output fuse Alarm open. (Red) Solar converter addresses contradictory. Fan not operating (solar converter Flashing shuts down). Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
Certain functions (i.e. solar converter addressing) may require adjustment when adding or replacing a solar converter module. Refer to the Power System documentation for instructions. Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
• Power Indicator (Green) Off • Protection Indicator (Yellow) ON • Protection Indicator (Yellow) Flashing • Alarm Indicator (Red) ON • Alarm Indicator (Red) Flashing Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
Page 23
(Red) On fuse open. Solar converter addresses Replace the solar converter. contradictory. Alarm Fan not operating Indicator (solar converter shuts Replace the fan. (Red) Flashing down). Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
Enable the external alarms, or notify appropriate personnel that this procedure is finished. Ensure that there are no local or remote alarms active on the system. Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
Page 25
Reinstall the solar converter and again check for proper airflow. Enable the external alarms, or notify appropriate personnel that this procedure is finished. Ensure that there are no local or remote alarms active on the system. Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
Page 26
Figure 8: Fan Replacement Align holes in fan with tabs on faceplate. Faceplate Mounting Screws (3) Faceplate Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...
Page 27
This page is intentionally blank. Vertiv | eSure™ MPPT Solar Converter Module User Manual (UM1S482000E3) | Rev. J...