8 •
750-613 [24 V DC Bus Power Supply]
Display Elements
Both the potential groups and the individual modules within these groups can
be arranged in any combination when designing the field bus node.
The supply voltage for the field side is made automatically through the
individual I/O modules by means of power jumper contacts.
Warning
The maximum current of the supply module is 10 A. When configuring the
system it is important not to exceed the maximum/sum current. However, if
such a case should occur, another supply module must be added.
The supply module 750-613 can be used with all couplers/controllers of the
WAGO-I/O-SYSTEM 750.
Attention
The supplementary power supply regulations (chapter 0, "
Power supply concept") must be observed for the certified operation of the
supply module 750-613 in shipbuilding or offshore and onshore applications!
2.1.1.3
Display Elements
A
B
Fig. 2.1.1-2: Display
Elements
g062602x
or
Fig. 2.1.1-3: Display
Elements
g062602x
LED
13 14
A
A
voltage supply
C
B
green
D
B
or
*)
C
green
*)
LED position is manufacturing dependent
Designation
State Function
No DC 24 V system voltage
off
supply.
Status
–
System
on
DC 24 V system voltage supply.
No DC 24 V voltage supply via
off
Status voltage
power jumper contacts.
supply
–
Power jumper
DC 24 V voltage supply via power
contacts.
on
jumper contacts.
WAGO-I/O-SYSTEM 750
I/O Modules