Notes on setpoint
adjustment (LTE mode
with Synco only)
Setpoint priority,
Setpoint Master RMB
Local configuration
RDF800KN..,
RDF800KN/VB only
Note:
26 / 94
Siemens
Smart Infrastructure
·
Setting the Comfort basic setpoint resets the runtime Comfort setpoint to the
basic setpoint.
·
Central setpoint shift is used for summer or winter compensation.
·
Setpoint shift does not affect the parameter setpoints in P08, P11, P12 and
P33.
·
Local shift and central shift are added together.
·
Only applies to Comfort and Economy setpoints. Protection setpoints are not
shifted centrally.
·
The current setpoints for heating and cooling are limited by the Protection
setpoint. If the Protection setpoint is OFF, min. 5 °C and max. 40 °C are used.
·
The setpoints for cooling and heating of the same operating mode have a
minimum distance of 0.5 K between them.
·
The result of local and central shift, together with the room operating mode, is
used by the thermostat for room temperature control (current setpoint).
·
The room thermostat always adopts the received setpoints from the controller
RMB795B. Thus the Comfort setpoints locally adjusted on the thermostats are
overwritten by the Comfort setpoints of the room group (e.g. every 15 minutes).
On the RMB795B central control unit (software version 2.0 or higher), you can
define the conditions required for the unit to forward the setpoints:
·
Always (every 15 minutes)
·
Not in Comfort mode
·
Only when changed
See "Setpoint priority" and "Setpoint master" functions on the RMB795B.
3.4

Applications overview

The thermostats support the following applications, which can be configured using
the DIP switches inside the front panel of the unit or a commissioning tool.
1. Set applications via DIP switches.
2. After the thermostat is first powered
up, the display depends on the
selected application.
à
Go to the setting mode and configure
the basic control parameters
For RDD810KN/NF, APP H displays after powering up.
RDF800KN.., RDF800KN/VB, RDD810KN/NF
Display
APP
2P
APP
2PEH
APP
4P
APP
2P3P
Basic documentation
Applications
2-pipe
2-pipe with
electric heater
4-pipe
2-pipe with 3-
position output
CE1P3174en
2020-02-21