Operational data
Environmental
conditions
Standards and
directives
Environmental
compatibility
General
Siemens
Smart Infrastructure
Switching differential, adjustable
Heating mode
Cooling mode
RDF800KN/VB, RDD810KN only)
Setpoint setting and range
Comfort
Economy
Protection
Multifunctional input X1/X2 for RDF800KN..,
RDF800KN/VB, RDD810KN
Multifunctional input X1/X2 for RDD810KN/NF
Input X1 default value
Input X2 default value
Built-in room temperature sensor
Measuring range
Accuracy at 25 °C
Temperature calibration range
Settings and display resolution
Setpoints
Current temperature value displayed
Operation
Climatic conditions
Temperature
Humidity
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
Storage
Climatic conditions
Temperature
Humidity
EU Conformity (CE)
Electronic control type
RCM conformity to EMC emission standard
Safety class
Pollution class
Degree of protection of housing
Housing flammability class according to UL94
The product environmental declaration CB1E3174xx contains data on
environmentally compatible product design and assessments (RoHS compliance,
materials composition, packaging, environmental benefit, disposal).
Connection terminals
Wiring cross section on
L, N, Q1, Q2, Q3, Y1, Y2
RDF800KN.., RDF800KN/VB, RDD810KN/NF
(P30)
(P31 for RDF800KN..,
(P08)
(P11-P12 for RDF800KN..,
RDF800KN/VB,RDD810KN)
(P11 for RDD810KN/NF)
(P65-P66)
(P38)
(P40)
Basic documentation
2 K (0.5...6 K)
1 K (0.5...6 K)
21 °C (5...40 °C)
15 °C/30°C (OFF, 5...40 °C)
15 °C/30°C (OFF, 5...40 °C)
8 °C/OFF
(OFF, 5...40 °C)
Selectable 0...8, 10
Selectable 0, 1, 3, 6, 7, 8, 10
3 (window contact)
1 (external temperature
sensor)
0...49 °C
< ± 0.5 K
± 3.0 K
0.5 °C
0.5 °C
As per IEC 60721-3-3
Class 3K5
0...50 °C
<95 % r.h.
As per IEC 60721-3-2
Class 2K3
-25...65 °C
<95 % r.h.
Class 2M2
As per IEC 60721-3-1
Class 1K3
-25...65 °C
<95 % r.h.
*)
8000078258_xx
2.B (micro-disconnection on
operation)
AS/NZS 61000-6-3
II as per EN 60730
Normal
IP 30 as per EN 60529
V-0
Solid wires or prepared
stranded wires
2
1 x 0.4...1.5 mm
or
2 x for KNX cables/sensor
2
Min 1.5 mm