Mechanical Installation

General Recommendations

WARNING: Risk of electric shock. Disconnect the appliance from electric supply before
commencing installation.
Note: Mechanical installation must conform to local codes and regulations.

Location

WARNING: The SKE4 series is designed for indoor installation only.
For outdoor installation, the SKE4 must be installed using a Neptronic weather proof
enclosure (see Positioning and Mounting - Weather Proof Enclosure Unit on page 17).
Failure to follow these guidelines will void the warranty.
Consider the following points before deciding the location for the SKE4 Steam Humidifier:
Plan a location that is easy to access and permits an easy inspection and servicing of the
humidifier.
Do not install the humidifier where failure of the appliance could cause damage to the
building structure or to other expensive equipment.
Ensure that the location is well ventilated and that the ambient temperature is less than
30°C.
Consider the total steam line length between the humidifier and the steam distributor
based on the steam line material type:
For flexible steam hose, total steam line must not exceed 5 meters. For longer
o
distances, use insulated hard piping.
For insulated hard piping, the total steam line is determined by the humidifier
o
capacity: 0.67 m for each kg/hr capacity of the humidifier, with a maximum of 15 m.
For longer steam line runs, consult factory.