Steam Dispersion System; Steam Dispersion System Selection - Neptronic SKE4-E Series Installation Instructions And User Manual

Steam humidifier
Hide thumbs Also See for SKE4-E Series:
Table of Contents

Advertisement

SKE4-E Steam Humidifier
Installation Instructions and User Manual

Steam Dispersion System

Steam Dispersion System Selection

In order to prevent the accumulation of condensation in air ducts, Neptronic has designed four basic
configurations of steam distribution systems to provide the most economical solution for any particular
application.
Steam Absorption Manifold (S.A.M.) Horizontal Duct
The S.A.M. system is suitable for installations where absorption distances are short, less than 1500
mm, and/or low duct temperatures are in effect.
Illustration 13 - Steam Absorption Manifold (S.A.M) Horizontal Duct
Steam Absorption Manifold (S.A.M.E2) Horizontal Duct
The S.A.M.E2 system is suitable for installations where absorption distances are short, less than 1500
mm, and/or low duct temperatures are in effect. S.A.M.E2 are used in applications with restricted duct
dimensions.
90
0
Illustration 14 - Steam Absorption Manifold (S.A.M.E2) Horizontal Duct
www.neptronic.com